19
We reserve the right to modify technical specifications without prior notice.
UK830504/210627
© Alpha-InnoTec GmbH
disCharge hot water safety valve and
Condensate disCharge
The discharge of the heating water safety valve and the
condensation water from the air must be drained via the
pre-mounted hoses in the unit in accordance with the
applicable standards and regulations. discharge of the
condensate and the safety valve into the sewage system
is permitted only via a funnel siphon, which must be
accessible at all times.
for positioning of the connection for condensate
discharge, see dimensional drawings for the
respective model.
1 drainage hose from hot
water safety valve
2 Hose for condensate discharge
CautIon!
guide the pre-mounted hose in the unit
for condensate discharge in the interior of
the unit as a siphon.
manometer
1 connection fitting
If necessary, the manometer can be separated from the
heating circuit
without
the need to drain the heating
circuit. for this purpose, unscrew the connection fitting
from the
automatic
shut-off valve.
CautIon.
Do not bend the capillary tube of the
manometer!
notICe.
there may be water splashes when you
screw and screw the fitting! use a torque
wrench to tighten the connection fitting -
torque: 10 nm.
Содержание LWC 100
Страница 56: ......