background image

900-0125-12-01 Rev A

 

©2017 OutBack Power Technologies.  All Rights Reserved.

 Page 34

 Page 35

M-3 High Battery Transfer (HBX)

In High Battery Transfer (HBX) mode, the system is connected to an 
AC source such as the utility grid; however, it will use battery power 
as the first priority.  The AC source is locked out until needed.  

In this mode, the system runs on DC power for as long as the batteries can be sustained.  It is expected 
that the batteries will be charged from renewable sources such as PV power.  When the batteries become 
depleted, the system reconnects to the AC source to operate the loads.  

The batteries may be recharged during this time using the renewable source.  When the batteries are 
recharged to a high enough voltage, the system transfers back to the batteries as the primary source 
(hence the name High Battery Transfer). 

HBX Mode commands the inverter to:

o

Connect to an AC source if the battery voltage has fallen below the 

Grid Connect

 voltage for the amount of time

set in the (connect) 

Delay

 

set point

o

Connect to an AC source if the battery state of charge (SOC) has fallen below the 

Grid Connect SOC

 for any

amount of time

o

Disconnect the AC source and switch to powering the loads from the battery bank if the battery voltage has risen
above the 

Grid Disconnect

 

voltage for the amount of time set in the (disconnect) 

Delay

 

set point

o

Disconnect the AC source and switch to powering loads from the battery bank if the battery state of charge (SOC)
has risen above the 

Grid Disconnect SOC

 for any amount of time

IMPORTANT:

  



HBX 

mode will control the master inverter in port 1 of a HUB Communications Manager.

The master will then instruct all subphase masters and slaves to connect or disconnect from the 
AC input source. 



For best operation, the inverter’s charger should be turned off when 

HBX

 mode is in use.

This mode is intended for systems that rely primarily on the renewable energy source for charging. 
The settings of 

HBX 

mode allow it to disconnect from the utility grid whenever it can charge 

effectively using the renewable source.  Use of the inverter's charger may interfere with these 
priorities.  This may keep both 

HBX 

mode and the inverter's charger from working effectively.  

See the 

MATE3s Overview Guide

 (the 

CHARGER 

hot key) for instructions on shutting off 

the charger. 

System Voltage

12 V

High Voltage

13

Low Voltage

12

24 V

36 V

26

38

24

36

48 V

52

48

Time

1 hour

1 hour

1 hour

1 hour

HBX Mode Default Set Points

NOTES ON SELECTING HBX MODE

:  



HBX 

mode has similar priorities to the 

Mini Grid 

mode used by FXR-class and Radian-class inverters. 

However, it is not compatible with 

Mini Grid 

and cannot be used at the same time.  To prevent conflicts 

when using 

HBX 

mode, make certain not to select 

Mini Grid

.  (Selection of AC input modes can be found on

 

page 11.  Information on 

Mini Grid

 and other modes can be found in the inverter

 Operator’s Manual

.)



HBX 

is also incompatible with the 

Grid Use Time 

and 

Load Grid Transfer 

functions in the MATE3s.  These 

functions do not have similar priorities to 

Mini Grid 

or 

HBX

, but they do control the inverter’s connection and 

disconnection with the grid.  

HBX 

should not be used with these functions.  (See pages 36 and 37.)



When deciding whether to use 

Mini Grid 

mode or 

HBX

, the user should consider the aspects of each.

– 

Mini Grid 

logic is based in the FXR inverter and can function in the absence of the MATE3s.  

HBX 

logic is based in

the MATE3s and cannot function unless the MATE3s is installed and operating.

– 

Mini Grid 

can use utility grid power to fully recharge the batteries every time it reconnects to the grid.

HBX 

can only do so under specific circumstances.

– 

HBX 

set points have a wide range of settings. 

Mini Grid 

uses settings intended to protect the batteries from

excessive discharge; however, most of its settings are automatic and do not allow customization.

– 

HBX 

works more efficiently with a larger renewable source, but there is no specification for renewable size.

Mini Grid 

cannot work properly unless the source is larger than the size of the loads. If this condition is not met,

Mini Grid 

will not disconnect the inverter from the utility grid.

Menu Items



Enabled/Disabled



Grid Connect

 — 

xx.x

 VDC (inverter-dependent)

The low-voltage level that causes the system to reconnect to the utility grid.



(Grid Connect) Delay

 — 

0

 to 

240

 

minutes

The delay period after reaching 

Grid Connect

 before the system reconnects to the utility grid.



Grid Disconnect

 — 

xx.x

 VDC (inverter-dependent)

The high-voltage level that causes the system to disconnect from the utility grid.



(Grid Disconnect) Delay

 — 

0

 to 

240

 

minutes

The delay period after reaching 

Grid Disconnect

 before the system disconnects from the utility grid.



Grid Connect

 

SOC

 — 

10

to 

100

%

The low-battery state of charge that causes the system to reconnect to the utility grid immediately.



Grid Disconnect SOC

 — 

50

%

 to 

100

%

The high-battery state of charge that causes the system to disconnect from the utility grid immediately.

NOTES ON SETTINGS

:



The system must be in the 

Grid Disconnect

 state to allow HBX default settings to be changed.



The 

Delay

 

set points are used to prevent the inverter from switching to grid power in the event of a sudden, 

sizable demand for power that may momentarily drop the voltage below the 

Grid Connect 

value.



The 

SOC

 

set points are only usable by a system equipped with a battery monitor. 

HBX

MATE3s Settings

Содержание Out Back Power MATE3s

Страница 1: ...CK POWER TECHNOLOGIES a MAKES NO WARRANTY AS TO THE ACCURACY SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION b ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE WHETHER DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S...

Страница 2: ...stop a generator The MATE3 allows a user to view monitor and establish all the settings and values that occur while the system is running Occasionally components may be added or upgraded electrical loads increase or patterns of usage may change These settings and values can be adjusted to match On screens with set points the control wheel E serves two functions navigation and set point adjustment ...

Страница 3: ...ommended Programming Order It is recommended that programming proceed in the following order 1 Establish Profile Wizard settings W 4 2 Save the Profile as applicable in either W 1 W 2 or W 3 3 Program the Profile as applicable in either W 1 W 2 or W 3 4 Program any other custom settings 5 Save the System Configuration S 2 6 When restoring settings in the future restore the System Configuration ins...

Страница 4: ...s when a button is pushed or the control wheel is used Button Beep Enabled or Disabled Wheel Click Enabled or Disabled IMPORTANT Some features are dependent on time and date settings Be sure to adjust these settings for the proper time and date for the location of the installation The MATE3s clock does not automatically adjust for daylight savings time The MATE3s does automatically adjust for leap...

Страница 5: ... maximum This name is displayed on the Home screen Set User Access Level A This menu allows one of four different user access levels UAL to set points for programming Full Access Level 1 UAL1 This allows full access to all available menus This is the same access permitted by the installer password It is the default setting Advanced Access Level 2 UAL2 This allows access to many user menus It also ...

Страница 6: ... Gen AC Input Voltage Limits FX class Pulse Spacing Adjusts the time between search pulses in single AC cycles Shorter spacing will detect loads more quickly This consumes more power o I 8 Auxiliary Output Relay o I 9 Inverter Stacking o I 10 Power Save Ranking o I 11 Grid Tie Sell B A C D I 3b Grid and Gen Input Voltage Limits FX class only The inverter will not connect to an AC source unless spe...

Страница 7: ...epicted On activates the AUX output immediately It displays Manual On and remains continuously active until Off is selected Auto activates the AUX output according to the Aux Mode automatic criteria When activated it displays Auto On otherwise it displays Auto Off Off deactivates the AUX output It displays Manual Off Note that the AUX output may still activate from the settings of inverter or MATE...

Страница 8: ...nverter for the L2 output in a split phase system B Phase C Phase Master The subphase master inverters for the B or C outputs in a three phase system 3p Master or 3phase Master The primary inverter for three phase systems that include the selection 1 2ph Master as shown above The 3p Master is Phase A 3phase Classic B C or 3p OB Slave A B C A secondary inverter for three phase systems Used in model...

Страница 9: ... will appear Pressing this key returns the screen to the Inverter menu NOTE Some items are retained at the present setting even when the inverter is reset to factory defaults The retained settings include the Output Voltage all items in the Calibrate menu Model Select and all items in the Grid Interface Protection menu This menu contains sensitive inverter settings Some settings relate to regional...

Страница 10: ...ler Owner s Manual features this as an option under RTS Compensation Limited Lower and Upper Battery Voltage Adjust the lowest and highest allowed compensated voltage The Owner s Manual features these as an option under RTS Compensation See page 42 for the effects of the Profile Wizard on both settings C 4 Battery Equalize CAUTION Battery Damage Do not equalize any sealed battery types VRLA AGM Ge...

Страница 11: ... reaching Disconnect Disconnect Delay The time after reaching Disconnect before the output is activated Float activates the AUX output when the charge controller enters the Float stage It can operate a charged indicator Not depicted No settable parameters Remote allows the AUX output to be activated by manual or automatic commands based in the MATE3s such as AGS Not depicted No settable parameters...

Страница 12: ...tivates the relay by automatic criteria according to the option selected in Relay Set Points Off deactivates the relay and prevents any of the FLEXnet Relay Set Points options from working Note that even if the relay output is set to Off it may still be activated by an external option such as AGS See page 25 Invert Logic Switches the relay s function from N O a normally open state to N C a normall...

Страница 13: ...ect to the inverter s GEN terminal input when using AGS If the input priority is set to GRID and the GRID terminals are energized an automatically controlled generator will shut down AGS turns on the inverter s charger even if it had previously been manually disabled AGS Topics These menus show the different topics settings and starting conditions for AGS AGS screens and topics included under M 1 ...

Страница 14: ...nge varies with battery voltage NOTE The Quiet Time settings overrides the settings and prevents an automatic start The exception is 2 Minute Start As an emergency set point it will start the generator regardless of Quiet Time settings Enabled either enables Y or disables N the Load Start function Start the load size 0 to 50 kW which requires the generator to start following the Delay time 1 to 24...

Страница 15: ...ints Voltage Load Must Run Exercise etc preventing the generator from starting automatically The only exception is 2 Minute Start which is considered an emergency start set point and which will start the generator regardless of Quiet Time settings M 1 AGS continued Set Generator Total Run Time The total running time for an automatic generator is displayed on the Generator Status screen which is ac...

Страница 16: ... shows the reason for starting under Last Run The first two columns in the table below are a list of start reasons The remaining columns display the possible reasons for the generator to stop The possible stop reasons are connected to the start reasons For example a generator which started due to Load kW can stop due to reduction of load kilowatts due to Quiet Time or manually However it will not ...

Страница 17: ...ogging to the SD card It does not turn off data logging to the internal flash memory Compact records only the minutes and seconds for each interval recorded SD Card DataLog Write Interval the interval 1 to 60 seconds at which data is automatically downloaded to the SD card SD Card Icon Front Back SD Card Clearance The data log shown in this example is arranged by date and time It shows all devices...

Страница 18: ...ters However it is not compatible with Mini Grid and cannot be used at the same time To prevent conflicts when using HBX mode make certain not to select Mini Grid Selection of AC input modes can be found on page 11 Information on Mini Grid and other modes can be found in the inverter Operator s Manual HBX is also incompatible with the Grid Use Time and Load Grid Transfer functions in the MATE3s Th...

Страница 19: ...e If a start time equals a stop time no action will be taken and the time period is ignored If the battery voltage falls below the inverter s Low Battery Cut Out voltage the inverter will automatically connect to the AC input source regardless of the time of day setting M 5 Load Grid Transfer The MATE3s can force all inverters to automatically reconnect to the utility grid even if the normal mode ...

Страница 20: ...active function to be turned off at midnight each night This function allows the charge controllers to complete a charge cycle at the beginning of the next day before the system begins selling It prevents the batteries from remaining at or below the Sell voltage for extended periods without receiving a full charge If grid interactive inverters are not present this item is inoperative Options are N...

Страница 21: ... complete press Exit to return to the Main Menu K W 2 Using Existing Profiles If the most recent profile was lost or changed it can be retrieved from an SD card and applied to the system If the profile was not ideal any existing value can be changed before re applying the profile To apply a profile that was previously saved 1 From the Profile Wizard menu select Existing Profile This will take the ...

Страница 22: ...System Type B System Type Off Grid Grid Tied Backup System Voltage Vdc B C Array Wattage Battery Type FLA Gel AGM and Capacity Ah Wizard Generator Configuration F Generator Installed Y or N Generator Type AC or DC and Size kW Generator Start Manual or Auto AUX Output Port F G Wizard AC Configuration D AC Output Voltage Vac AC Phase Single Split 3 Phase AC Input Breaker Size Aac Maximum Output Load...

Страница 23: ...e new data log name Saving to SD Card will be displayed In either case C Wait for the confirmation screen to appear After the screen appears press Continue to return to Upload and Save Data Log B A C Date AH 0 38 kWh Max Amps 0 38 0 9 36 Max Watts 52 48 32 0 8 1 hour 1 hour FLEXmax Data Log 6 13 15 6 12 15 6 11 15 Absorb Time 0 00 0 00 0 00 Float Time 0 00 0 00 0 00 Min Battery V 24 1 24 1 24 1 Ma...

Страница 24: ...ard or deleted from the MATE3s internal memory o To Save an Event Log E 1 o To Read an Event Log File from the SD Card E 2 o To Delete an Event Log E 3 E 1 To Save an Event Log To create a data log for the FLEXmax Charge Controller 1 From the Event Logs menu select Save Events to SD Card 2 On the Date Range set point use the control wheel to select the date for the event log or logs to be saved to...

Страница 25: ... OutBack product to which it is connected The OutBack products may not be powered up or connected Symptom Possible Remedy Check all OutBack devices for correct operation Check or replace the CAT5 cable running from the MATE3s to the OutBack product The left hand RJ45 port on the back of the MATE3s is used for computer communications It cannot power a MATE3s Make sure the CAT5 cable is plugged into...

Страница 26: ...r Technologies All Rights Reserved 2 Check the LED indicator o A flashing EVENTS indicator means a warning has occurred o A solid EVENTS indicator may mean that the system has shut down due to an error If Advanced Generator Start AGS is in use it may also mean the system has suffered an AGS fault See the MATE3s Overview Guide and the inverter literature for more information on warnings and errors ...

Отзывы: