M-1. AGS continued

BATTERY STATUS

INVERTER

GEN

CHARGER

EVENTS

FAVORITE

AC INPUT

1.5 
kW

0.1 
kW

0.0 
kW

G

G

OutBack Power

1.5 kW
1.5 kW

115 V

1.5 kW

85%

28.5 V

System

OK

0.00 kW

0.0 kW

G

G



AGS Functional Test

Before any further programming, confirm that the generator is working properly.  Using the generator’s own

controls, manually turn it on and then shut it off.
Next, test the remote start functionality.  Go to the 

Generator Status

 screen using the 

GEN 

hot key.

To test the AGS function through the MATE3s:

1. Press the 

GEN 

hot key to bring up the 

Generator Status

 

screen.

2. Press the <

ON

> soft key and wait for the generator to start running.

3. Press the <

OFF

> soft key to shut the generator off.

4. Press the <

AUTO

> soft key to put the generator in 

AUTO 

mode.

(Automatic functions need to be tested separately.)

5. Press the

 

<

BACK

> soft key to return to the 

Home 

screen.



AGS Troubleshooting

If the generator fails to start or connect, there are many possible reasons.  The steps below provide

initial guidance for troubleshooting.

The AGS timers have not been activated by 
the present conditions.  

Check to make sure at least one AGS timer is active.  
(See page 29.)  If the timers are not active, check the 
AGS settings.  Compare all settings against the Start 
and Stop Reasons table.  (See page 31.)

AGS starts the generator 
but 

AGS Fault

 appears 

anyway.

Generator output does not meet inverter 
requirements.  

Check generator voltage and frequency.

To clear an AGS fault, go to the 

GEN 

hot key screen.  

Press the <

OFF

> soft key.  

A Stop condition is active.  This could include 
Quiet Time.  

AGS does not send a start 
command under expected 
conditions.

AGS is not enabled.

Check 

Mode 

in the 

GEN 

hot key screen.  Ensure 

AGS Enabled

 is set to 

Y

.  (See page 25.)  

Possible Cause

AGS sends a command 
but the generator does 
not start.

Open circuit between AUX connection and 
generator.  

Symptom

Possible Remedy

Ensure the generator will start using its own controls. 
Ensure it will start using the <

ON

> soft key in the 

GEN 

hot key screen.  Check all conductors, including 

external relays, contactors, or other devices.   

Compare all settings against the Start and Stop 
Reasons table.  (See page 31.)

Generator output is not reaching inverter input. 

Check all circuit breakers and switches.  Measure AC 
voltage at inverter input terminals.



Start and Stop Reasons

After AGS has started the generator, the 

GEN 

hot key screen shows

the reason for starting under 

Last Run

.   The first two columns in

the table below are a list of start reasons.
The remaining columns display the possible reasons for the generator to stop.  The possible stop reasons

are connected to the start reasons.  For example, a generator which started due to Load kW can stop due

to reduction of load kilowatts, due to Quiet Time, or manually.  However, it will not stop due to battery

state of charge (SOC) or any of the other reasons.

NOTES



"Setting" refers to the 

Interval Days

 setting in the 

State-of-Charge (SOC) Start 

screen as depicted on page 28.



“CPM” (Charged Parameters Met) refers to the full-charge parameters of the FLEXnet DC (FN-DC) Battery Monitor as defined

on page 22.  The FN-DC must be installed in the system.



The conditions of the 

Inverter In Float or Silent

 column will stop the generator if the inverter reaches these charging

stages before the conditions of the other columns take effect.



The conditions of the 

Stop SOC%

 column apply as long as 

Days Since Parms Met

 does not exceed

 Interval Days

.

The generator will be shut off upon reaching the 

Stop SOC%

 setting as shown on page 28.



The conditions of the 

Stop at 100% SOC

 column apply if 

Days Since Parms Met

 equals or exceeds 

Interval Days

.

The generator will ignore the 

Stop SOC%

 setting and continue running until the battery SOC is at 100%.  (This function does 

not operate if 

Enable Full Charge

 is set at 

N

, or if the 

Interval 

is set at 

0

.)



The conditions of the 

FN-DC Charge Parms Met (CPM)

 column apply when

 Days Since Parms Met

 equals or exceeds

Interval Days

 and 

Enable Full Charge

 (100% SOC) is disabled as noted above.  These conditions also apply if for any reason 

the charge parameters are not met when the batteries reach 100% SOC as noted above.  The generator will continue to run 

until the FN-DC's charge parameters have been met.

24 Hour Batt V

Yes

Stop

Stop if days 

since CPM 

< setting

Stop if days 

since CPM 

> setting

2 Hour Batt V

Yes

Stop

Stop if days 

since CPM 

< setting

Stop if days 

since CPM 

> setting

2 Min Batt V

Yes

Stop

Stop

Inverter 

in Float 

or Silent

START 

REASONS

Global 

Rebulk

Stop 

SOC %

FN-DC 

Charge 

Parms Met 

(CPM)

Below 

Load 

kW

Start SOC %

Yes

Stop

Stop if days 

since CPM 

< setting

Stop if days 

since CPM 

> setting

Load kW

Stop

Exercise

Must Run Start

Yes

Manual 

Yes

If Auto 

selected

If Auto 

selected

Stop if days 

since 100% 

> setting

Stop if days 

since 100% 

> setting

Stop at 

100% 

SOC 

Stop if days 

since 100% 

> setting

Stop

Stop

Quiet 

Time

Stop

Stop

Stop

Stop

Exercise 

Time 

Expires

Stop

Stop

Stop

Stop

Manual 

Stop

Stop

Stop

Stop

Stop

Stop

Stop

Stop

Stop

High 

Batt 

Voltage

Stop

Below 

Load 

kW

Stop

STOP REASONS

AGS (Testing)

MATE3s Settings

Содержание Out Back Power MATE3s

Страница 1: ...CK POWER TECHNOLOGIES a MAKES NO WARRANTY AS TO THE ACCURACY SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION b ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE WHETHER DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S...

Страница 2: ...stop a generator The MATE3 allows a user to view monitor and establish all the settings and values that occur while the system is running Occasionally components may be added or upgraded electrical loads increase or patterns of usage may change These settings and values can be adjusted to match On screens with set points the control wheel E serves two functions navigation and set point adjustment ...

Страница 3: ...ommended Programming Order It is recommended that programming proceed in the following order 1 Establish Profile Wizard settings W 4 2 Save the Profile as applicable in either W 1 W 2 or W 3 3 Program the Profile as applicable in either W 1 W 2 or W 3 4 Program any other custom settings 5 Save the System Configuration S 2 6 When restoring settings in the future restore the System Configuration ins...

Страница 4: ...s when a button is pushed or the control wheel is used Button Beep Enabled or Disabled Wheel Click Enabled or Disabled IMPORTANT Some features are dependent on time and date settings Be sure to adjust these settings for the proper time and date for the location of the installation The MATE3s clock does not automatically adjust for daylight savings time The MATE3s does automatically adjust for leap...

Страница 5: ... maximum This name is displayed on the Home screen Set User Access Level A This menu allows one of four different user access levels UAL to set points for programming Full Access Level 1 UAL1 This allows full access to all available menus This is the same access permitted by the installer password It is the default setting Advanced Access Level 2 UAL2 This allows access to many user menus It also ...

Страница 6: ... Gen AC Input Voltage Limits FX class Pulse Spacing Adjusts the time between search pulses in single AC cycles Shorter spacing will detect loads more quickly This consumes more power o I 8 Auxiliary Output Relay o I 9 Inverter Stacking o I 10 Power Save Ranking o I 11 Grid Tie Sell B A C D I 3b Grid and Gen Input Voltage Limits FX class only The inverter will not connect to an AC source unless spe...

Страница 7: ...epicted On activates the AUX output immediately It displays Manual On and remains continuously active until Off is selected Auto activates the AUX output according to the Aux Mode automatic criteria When activated it displays Auto On otherwise it displays Auto Off Off deactivates the AUX output It displays Manual Off Note that the AUX output may still activate from the settings of inverter or MATE...

Страница 8: ...nverter for the L2 output in a split phase system B Phase C Phase Master The subphase master inverters for the B or C outputs in a three phase system 3p Master or 3phase Master The primary inverter for three phase systems that include the selection 1 2ph Master as shown above The 3p Master is Phase A 3phase Classic B C or 3p OB Slave A B C A secondary inverter for three phase systems Used in model...

Страница 9: ... will appear Pressing this key returns the screen to the Inverter menu NOTE Some items are retained at the present setting even when the inverter is reset to factory defaults The retained settings include the Output Voltage all items in the Calibrate menu Model Select and all items in the Grid Interface Protection menu This menu contains sensitive inverter settings Some settings relate to regional...

Страница 10: ...ler Owner s Manual features this as an option under RTS Compensation Limited Lower and Upper Battery Voltage Adjust the lowest and highest allowed compensated voltage The Owner s Manual features these as an option under RTS Compensation See page 42 for the effects of the Profile Wizard on both settings C 4 Battery Equalize CAUTION Battery Damage Do not equalize any sealed battery types VRLA AGM Ge...

Страница 11: ... reaching Disconnect Disconnect Delay The time after reaching Disconnect before the output is activated Float activates the AUX output when the charge controller enters the Float stage It can operate a charged indicator Not depicted No settable parameters Remote allows the AUX output to be activated by manual or automatic commands based in the MATE3s such as AGS Not depicted No settable parameters...

Страница 12: ...tivates the relay by automatic criteria according to the option selected in Relay Set Points Off deactivates the relay and prevents any of the FLEXnet Relay Set Points options from working Note that even if the relay output is set to Off it may still be activated by an external option such as AGS See page 25 Invert Logic Switches the relay s function from N O a normally open state to N C a normall...

Страница 13: ...ect to the inverter s GEN terminal input when using AGS If the input priority is set to GRID and the GRID terminals are energized an automatically controlled generator will shut down AGS turns on the inverter s charger even if it had previously been manually disabled AGS Topics These menus show the different topics settings and starting conditions for AGS AGS screens and topics included under M 1 ...

Страница 14: ...nge varies with battery voltage NOTE The Quiet Time settings overrides the settings and prevents an automatic start The exception is 2 Minute Start As an emergency set point it will start the generator regardless of Quiet Time settings Enabled either enables Y or disables N the Load Start function Start the load size 0 to 50 kW which requires the generator to start following the Delay time 1 to 24...

Страница 15: ...ints Voltage Load Must Run Exercise etc preventing the generator from starting automatically The only exception is 2 Minute Start which is considered an emergency start set point and which will start the generator regardless of Quiet Time settings M 1 AGS continued Set Generator Total Run Time The total running time for an automatic generator is displayed on the Generator Status screen which is ac...

Страница 16: ... shows the reason for starting under Last Run The first two columns in the table below are a list of start reasons The remaining columns display the possible reasons for the generator to stop The possible stop reasons are connected to the start reasons For example a generator which started due to Load kW can stop due to reduction of load kilowatts due to Quiet Time or manually However it will not ...

Страница 17: ...ogging to the SD card It does not turn off data logging to the internal flash memory Compact records only the minutes and seconds for each interval recorded SD Card DataLog Write Interval the interval 1 to 60 seconds at which data is automatically downloaded to the SD card SD Card Icon Front Back SD Card Clearance The data log shown in this example is arranged by date and time It shows all devices...

Страница 18: ...ters However it is not compatible with Mini Grid and cannot be used at the same time To prevent conflicts when using HBX mode make certain not to select Mini Grid Selection of AC input modes can be found on page 11 Information on Mini Grid and other modes can be found in the inverter Operator s Manual HBX is also incompatible with the Grid Use Time and Load Grid Transfer functions in the MATE3s Th...

Страница 19: ...e If a start time equals a stop time no action will be taken and the time period is ignored If the battery voltage falls below the inverter s Low Battery Cut Out voltage the inverter will automatically connect to the AC input source regardless of the time of day setting M 5 Load Grid Transfer The MATE3s can force all inverters to automatically reconnect to the utility grid even if the normal mode ...

Страница 20: ...active function to be turned off at midnight each night This function allows the charge controllers to complete a charge cycle at the beginning of the next day before the system begins selling It prevents the batteries from remaining at or below the Sell voltage for extended periods without receiving a full charge If grid interactive inverters are not present this item is inoperative Options are N...

Страница 21: ... complete press Exit to return to the Main Menu K W 2 Using Existing Profiles If the most recent profile was lost or changed it can be retrieved from an SD card and applied to the system If the profile was not ideal any existing value can be changed before re applying the profile To apply a profile that was previously saved 1 From the Profile Wizard menu select Existing Profile This will take the ...

Страница 22: ...System Type B System Type Off Grid Grid Tied Backup System Voltage Vdc B C Array Wattage Battery Type FLA Gel AGM and Capacity Ah Wizard Generator Configuration F Generator Installed Y or N Generator Type AC or DC and Size kW Generator Start Manual or Auto AUX Output Port F G Wizard AC Configuration D AC Output Voltage Vac AC Phase Single Split 3 Phase AC Input Breaker Size Aac Maximum Output Load...

Страница 23: ...e new data log name Saving to SD Card will be displayed In either case C Wait for the confirmation screen to appear After the screen appears press Continue to return to Upload and Save Data Log B A C Date AH 0 38 kWh Max Amps 0 38 0 9 36 Max Watts 52 48 32 0 8 1 hour 1 hour FLEXmax Data Log 6 13 15 6 12 15 6 11 15 Absorb Time 0 00 0 00 0 00 Float Time 0 00 0 00 0 00 Min Battery V 24 1 24 1 24 1 Ma...

Страница 24: ...ard or deleted from the MATE3s internal memory o To Save an Event Log E 1 o To Read an Event Log File from the SD Card E 2 o To Delete an Event Log E 3 E 1 To Save an Event Log To create a data log for the FLEXmax Charge Controller 1 From the Event Logs menu select Save Events to SD Card 2 On the Date Range set point use the control wheel to select the date for the event log or logs to be saved to...

Страница 25: ... OutBack product to which it is connected The OutBack products may not be powered up or connected Symptom Possible Remedy Check all OutBack devices for correct operation Check or replace the CAT5 cable running from the MATE3s to the OutBack product The left hand RJ45 port on the back of the MATE3s is used for computer communications It cannot power a MATE3s Make sure the CAT5 cable is plugged into...

Страница 26: ...r Technologies All Rights Reserved 2 Check the LED indicator o A flashing EVENTS indicator means a warning has occurred o A solid EVENTS indicator may mean that the system has shut down due to an error If Advanced Generator Start AGS is in use it may also mean the system has suffered an AGS fault See the MATE3s Overview Guide and the inverter literature for more information on warnings and errors ...

Отзывы: