Quiet Time Schedule

This is a period of time when the generator is commanded not to run
regardless of other conditions.  

Quiet Time

 is usually set due to

the risk of inappropriate noise or other reasons.  

Quiet Time

 

can be

set individually for weekdays and weekends.

The 

Quiet Time

 

function is disabled when 

Start 

and 

Stop 

are set to the same time, or if 

Enable 

is set to 

N

.



Enable

 — either enables (

Y

) or disables (

N

) the 

Quiet Time 

function.



Weekday Start

 — the beginning time (

00:00

 to 

23:59

, Monday through Friday) when the generator is not allowed to start.



Weekday 

Stop

 — the ending time (

00:00

 to 

23:59

, Monday through Friday) after which the generator is allowed to start.



Weekend Start

 — the beginning time (

00:00

 to 

23:59

, Saturday and Sunday) when the generator is not allowed to start.



Weekend 

Stop

 — the ending time (

00:00

 to 

23:59

, Saturday and Sunday) after which the generator is allowed to start.



Generator Exercise Schedule

This is a period of time when the generator is scheduled to run briefly

regardless of other conditions.  The exercise function can operate once a

week or every few weeks.



Enable

 — either enables (

Y

) or disables (

N

) the 

Exercise 

function.



Exercise Run on

 — the day of the week (

Mon

 to 

Sun

) when 

Generator Exercise

 is scheduled.



Start Time

 — the time (

00:00

 to 

23:59

) at which the generator starts.



Run Period

 — the duration (

1

 to 

240

 minutes) of the exercise period.



Exercise Interval

 — the number of weeks (

0

 to 

8

) that will pass between exercise periods.



Disable Sell During Exercise 

— either prohibits (Y) or permits (N) a grid-interactive model from selling power during the

exercise period.  This is mostly applicable to DC generators.   

IMPORTANT:

  

Regularly running a generator keeps engine components lubricated, expels excess moisture, charges 

the starting battery, and helps prevent carbon build-up.  Consult the generator owner’s manual for the 

appropriate length and frequency of exercise periods and what load to run during the exercise period.  

IMPORTANT:

  

Quiet Time

 overrides most of the starting set points (

Voltage

Load

Must Run

Exercise 

etc.), 

preventing the generator from starting automatically.  The only exception is 

2 Minute Start

which is considered an “emergency” start set point and which will start the generator regardless of 

Quiet Time

 settings.  

M-1. AGS continued



Set Generator Total Run Time

The total running time for an automatic generator is displayed on
the 

Generator Status

 screen, which is accessed with the 

Gen 

hot

key.  (See the

 MATE3s Overview Guide

.)  If the existing total is

inaccurate in some way, it may need to be corrected or reset.  This
menu allows the timer to be set to a different figure.  It can also be
reset to zero.



Generator Total Run Time

 

 – 

0.0

  

to 

999.9 hours



AGS Timers

This is a read-only screen that displays times and values for the MATE3s
functions described on the preceding pages.  Programming of these
values is done in the 

Quiet Time

 

Schedule

Voltage Start

Load Start

,

Must Run Schedule

or

 

State of Charge Start

 menus described on

the previous page.



Fault

 

begins counting from zero when no voltage is detected after a generator start.  When the 

Fault Time

 setting is

reached according to the 

AGS Setup

 screen on page 25, an AGS fault will be generated.  An event will also be recorded. 

(See page 47).



Warmup

Cooldown

, and 

Exercise

 

begin counting from zero when each stage begins.  The generator will react

accordingly when their respective times are reached according to the 

AGS Setup

 screen on page 25.



2 Min

2 Hour

, and 

24 Hour

 

begin counting down from the maximum time when the respective conditions are reached for

each setting.  If any of these timers reach zero, the generator will be started.



Load Start

 

and 

Load Stop

 begin counting from zero when the respective conditions are reached for each setting.  If

either of these timers reach the delay time as set in the 

Load Start

 

screen on page 28, the generator will be started or 

stopped as appropriate.



DC Absorb

 

is used with the DC generator settings shown on page 25.  It begins counting from zero when the 

DC Absorb

Voltage

 is reached.  The generator will be stopped when the 

DC Absorb Time

 setting is reached. 

 Page 28

900-0125-12-01 Rev A

 

©2017 OutBack Power Technologies.  All Rights Reserved.

 Page 29

AGS

MATE3s Settings

Содержание Out Back Power MATE3s

Страница 1: ...CK POWER TECHNOLOGIES a MAKES NO WARRANTY AS TO THE ACCURACY SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION b ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE WHETHER DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S...

Страница 2: ...stop a generator The MATE3 allows a user to view monitor and establish all the settings and values that occur while the system is running Occasionally components may be added or upgraded electrical loads increase or patterns of usage may change These settings and values can be adjusted to match On screens with set points the control wheel E serves two functions navigation and set point adjustment ...

Страница 3: ...ommended Programming Order It is recommended that programming proceed in the following order 1 Establish Profile Wizard settings W 4 2 Save the Profile as applicable in either W 1 W 2 or W 3 3 Program the Profile as applicable in either W 1 W 2 or W 3 4 Program any other custom settings 5 Save the System Configuration S 2 6 When restoring settings in the future restore the System Configuration ins...

Страница 4: ...s when a button is pushed or the control wheel is used Button Beep Enabled or Disabled Wheel Click Enabled or Disabled IMPORTANT Some features are dependent on time and date settings Be sure to adjust these settings for the proper time and date for the location of the installation The MATE3s clock does not automatically adjust for daylight savings time The MATE3s does automatically adjust for leap...

Страница 5: ... maximum This name is displayed on the Home screen Set User Access Level A This menu allows one of four different user access levels UAL to set points for programming Full Access Level 1 UAL1 This allows full access to all available menus This is the same access permitted by the installer password It is the default setting Advanced Access Level 2 UAL2 This allows access to many user menus It also ...

Страница 6: ... Gen AC Input Voltage Limits FX class Pulse Spacing Adjusts the time between search pulses in single AC cycles Shorter spacing will detect loads more quickly This consumes more power o I 8 Auxiliary Output Relay o I 9 Inverter Stacking o I 10 Power Save Ranking o I 11 Grid Tie Sell B A C D I 3b Grid and Gen Input Voltage Limits FX class only The inverter will not connect to an AC source unless spe...

Страница 7: ...epicted On activates the AUX output immediately It displays Manual On and remains continuously active until Off is selected Auto activates the AUX output according to the Aux Mode automatic criteria When activated it displays Auto On otherwise it displays Auto Off Off deactivates the AUX output It displays Manual Off Note that the AUX output may still activate from the settings of inverter or MATE...

Страница 8: ...nverter for the L2 output in a split phase system B Phase C Phase Master The subphase master inverters for the B or C outputs in a three phase system 3p Master or 3phase Master The primary inverter for three phase systems that include the selection 1 2ph Master as shown above The 3p Master is Phase A 3phase Classic B C or 3p OB Slave A B C A secondary inverter for three phase systems Used in model...

Страница 9: ... will appear Pressing this key returns the screen to the Inverter menu NOTE Some items are retained at the present setting even when the inverter is reset to factory defaults The retained settings include the Output Voltage all items in the Calibrate menu Model Select and all items in the Grid Interface Protection menu This menu contains sensitive inverter settings Some settings relate to regional...

Страница 10: ...ler Owner s Manual features this as an option under RTS Compensation Limited Lower and Upper Battery Voltage Adjust the lowest and highest allowed compensated voltage The Owner s Manual features these as an option under RTS Compensation See page 42 for the effects of the Profile Wizard on both settings C 4 Battery Equalize CAUTION Battery Damage Do not equalize any sealed battery types VRLA AGM Ge...

Страница 11: ... reaching Disconnect Disconnect Delay The time after reaching Disconnect before the output is activated Float activates the AUX output when the charge controller enters the Float stage It can operate a charged indicator Not depicted No settable parameters Remote allows the AUX output to be activated by manual or automatic commands based in the MATE3s such as AGS Not depicted No settable parameters...

Страница 12: ...tivates the relay by automatic criteria according to the option selected in Relay Set Points Off deactivates the relay and prevents any of the FLEXnet Relay Set Points options from working Note that even if the relay output is set to Off it may still be activated by an external option such as AGS See page 25 Invert Logic Switches the relay s function from N O a normally open state to N C a normall...

Страница 13: ...ect to the inverter s GEN terminal input when using AGS If the input priority is set to GRID and the GRID terminals are energized an automatically controlled generator will shut down AGS turns on the inverter s charger even if it had previously been manually disabled AGS Topics These menus show the different topics settings and starting conditions for AGS AGS screens and topics included under M 1 ...

Страница 14: ...nge varies with battery voltage NOTE The Quiet Time settings overrides the settings and prevents an automatic start The exception is 2 Minute Start As an emergency set point it will start the generator regardless of Quiet Time settings Enabled either enables Y or disables N the Load Start function Start the load size 0 to 50 kW which requires the generator to start following the Delay time 1 to 24...

Страница 15: ...ints Voltage Load Must Run Exercise etc preventing the generator from starting automatically The only exception is 2 Minute Start which is considered an emergency start set point and which will start the generator regardless of Quiet Time settings M 1 AGS continued Set Generator Total Run Time The total running time for an automatic generator is displayed on the Generator Status screen which is ac...

Страница 16: ... shows the reason for starting under Last Run The first two columns in the table below are a list of start reasons The remaining columns display the possible reasons for the generator to stop The possible stop reasons are connected to the start reasons For example a generator which started due to Load kW can stop due to reduction of load kilowatts due to Quiet Time or manually However it will not ...

Страница 17: ...ogging to the SD card It does not turn off data logging to the internal flash memory Compact records only the minutes and seconds for each interval recorded SD Card DataLog Write Interval the interval 1 to 60 seconds at which data is automatically downloaded to the SD card SD Card Icon Front Back SD Card Clearance The data log shown in this example is arranged by date and time It shows all devices...

Страница 18: ...ters However it is not compatible with Mini Grid and cannot be used at the same time To prevent conflicts when using HBX mode make certain not to select Mini Grid Selection of AC input modes can be found on page 11 Information on Mini Grid and other modes can be found in the inverter Operator s Manual HBX is also incompatible with the Grid Use Time and Load Grid Transfer functions in the MATE3s Th...

Страница 19: ...e If a start time equals a stop time no action will be taken and the time period is ignored If the battery voltage falls below the inverter s Low Battery Cut Out voltage the inverter will automatically connect to the AC input source regardless of the time of day setting M 5 Load Grid Transfer The MATE3s can force all inverters to automatically reconnect to the utility grid even if the normal mode ...

Страница 20: ...active function to be turned off at midnight each night This function allows the charge controllers to complete a charge cycle at the beginning of the next day before the system begins selling It prevents the batteries from remaining at or below the Sell voltage for extended periods without receiving a full charge If grid interactive inverters are not present this item is inoperative Options are N...

Страница 21: ... complete press Exit to return to the Main Menu K W 2 Using Existing Profiles If the most recent profile was lost or changed it can be retrieved from an SD card and applied to the system If the profile was not ideal any existing value can be changed before re applying the profile To apply a profile that was previously saved 1 From the Profile Wizard menu select Existing Profile This will take the ...

Страница 22: ...System Type B System Type Off Grid Grid Tied Backup System Voltage Vdc B C Array Wattage Battery Type FLA Gel AGM and Capacity Ah Wizard Generator Configuration F Generator Installed Y or N Generator Type AC or DC and Size kW Generator Start Manual or Auto AUX Output Port F G Wizard AC Configuration D AC Output Voltage Vac AC Phase Single Split 3 Phase AC Input Breaker Size Aac Maximum Output Load...

Страница 23: ...e new data log name Saving to SD Card will be displayed In either case C Wait for the confirmation screen to appear After the screen appears press Continue to return to Upload and Save Data Log B A C Date AH 0 38 kWh Max Amps 0 38 0 9 36 Max Watts 52 48 32 0 8 1 hour 1 hour FLEXmax Data Log 6 13 15 6 12 15 6 11 15 Absorb Time 0 00 0 00 0 00 Float Time 0 00 0 00 0 00 Min Battery V 24 1 24 1 24 1 Ma...

Страница 24: ...ard or deleted from the MATE3s internal memory o To Save an Event Log E 1 o To Read an Event Log File from the SD Card E 2 o To Delete an Event Log E 3 E 1 To Save an Event Log To create a data log for the FLEXmax Charge Controller 1 From the Event Logs menu select Save Events to SD Card 2 On the Date Range set point use the control wheel to select the date for the event log or logs to be saved to...

Страница 25: ... OutBack product to which it is connected The OutBack products may not be powered up or connected Symptom Possible Remedy Check all OutBack devices for correct operation Check or replace the CAT5 cable running from the MATE3s to the OutBack product The left hand RJ45 port on the back of the MATE3s is used for computer communications It cannot power a MATE3s Make sure the CAT5 cable is plugged into...

Страница 26: ...r Technologies All Rights Reserved 2 Check the LED indicator o A flashing EVENTS indicator means a warning has occurred o A solid EVENTS indicator may mean that the system has shut down due to an error If Advanced Generator Start AGS is in use it may also mean the system has suffered an AGS fault See the MATE3s Overview Guide and the inverter literature for more information on warnings and errors ...

Отзывы: