PV Junction Box Data Check
Click on stored energy system list -> input SN -> click operating data -> Check by choosing
the required operating data type.
Emergency Stop
When the energy storage system is abnormal, you can press the emergency stop button
"EPO" on the cabinet door, turn off the diesel engine switch, load switch, PV switch and
battery switch.
In order to prevent personal injury, if you want to repair or open the machine after power-
off, please measure the voltage at the input port with the multimeter at the first. Before the
relevant operation, please confirm that there is no grid electric supply!
The upper cover plate cannot be opened until the DC-link capacitance inside the module
discharges completely about 15 minutes later (see warning label on the surface of module
for details).