1. When the SOC drops below the lower limit of the configured SOC range, the diesel
generator will start; when it raises beyond the upper limit, the diesel generator will then be
turned off.
2. Charging power mode
If the mode 6
-
battery charging power mode is selected, the diesel generator will charge
the batteries with the configured power;
3. Diesel generator rated power mode
If the mode 7
–
diesel generator output rated power mode is selected, the diesel generator
will charge to the batteries with the rest power under the condition of satisfying load.
The rest power is P
rest
= P
output
– P
load
.
You can also set the control mode on the website, see 5.5.3
Online Monitoring
Register
You have to create a new account on our webserver for the normal monitoring. In addition,
a part of our warranty is based on this connection to our webserver. The data before the
registration would not be retained on the webserver.
So please use the following steps:
Open the portal: www.alphaess.com.
Please fill in “Username”, “Password” and click “Login”, if you have registered.
If not, please register following these steps
Figure 5-5 Monitoring Login Interface