Alpha ESS Co., Ltd.
Page 33 of 45
Your Smart Energy
Figure 5-8 System Registering Interface
Input
S/N
,
Check Code
,
License No
.,
Date
,
Name
, and
Contact No.
to complete the
registering process.
Generator Control Setting On Server
You can set according to the actual conditions by customers.
There are two options, SOC control or time control.
At the first, please click Generator to enable it.
Choose SOC control to set SOC range. If the SOC drops below the lower limit of the
configured SOC range, the diesel generator will start; when it raises beyond the upper
limit, the diesel generator will then be turned off.
If you set the battery charge power, it will charge the batteries with the configured
battery charge power.
If you set the Generator output power. it will charge the batteries with the rest power
under the condition of satisfying load. The rest power is P=P
output
– P
load
.
Choose time control, the diesel generator will start during the configured working
time.