______________________________________________________________________
Alpha ESS Co., Ltd.
Page 21 of 45
Your Smart Energy
2. The self-weight of the container is about 2 t, the accessories such as internal PCS are
about 1 t, one battery rack with batteries is about 700kg and the total weight of the system
is about 5.8 t.
3.
Foundation height is considered to be the highest historical water level of the area.
4. Two earthing points are provided outside the container.
5. People should be able to bend down and pull the cables under the
manhole so it’s better
that the height is not less than 1600mm (changeable according to the real situation).
6. Pay attention to the drainage of the inlet-outlet holes and the foundation.
4.2.1.2 Container Hoisting
Step1
:
Hoist the container to the corresponding foundation as the lifting plan.
NOTE
:
The lifting rope is fixed on the upper corner of the container B, B’, B’’, B’’’ and the
length of the four ropes are equal.
The hooks position should be on the top of the container. The length of the rope adapted
should ensure that the angle between the ropes and the roof of the container is greater than
60 degrees. Maintain the horizontal level of the container in the lifting process.
Step2:
Put it on a prepared foundation.
Step3:
Open the container emergency door.