background image

16 

Figure 12 for connecting 4-wire receivers. 
 

NOTE:  IF THE 4 WIRE RECEIVER INSTRUCTIONS SHOW 
THAT TWO OF THE WIRES ARE OF THE SAME COLOR 
AND ARE COMMON CONNECTIONS INSIDE THE 
RECEIVER, ONE OF THESE WIRES SHOULD BE 
CONNECTED TO TERMINAL #1 (COMMON) AND THE 
OTHER TO ONE SIDE OF THE TRANSFORMER. 
 

 

WIRING A 3-BUTTON STATION

 

See Figure 13 for instructions on wiring a 3-button station.  

NOTE: 

 

 The STOP button is normally OPEN. 

 

WIRING A KEYPAD OR TELEPHONE ENTRY 
SYSTEM 

 

Install according to the manufacturer's instructions. 

 

BI-PARTING APPLICATION 

 
 

In a bi-parting application, two operators are required, one operating in 
a left-hand mode, the other in a right-hand mode.  Both must be wired 
for AC power (as previously described)  but share  a common set of 
input controls.   In general, all of the preceding instructions concerning 
installation of individual operators can be followed in a bi-parting 
application except the following: 

 

Choose one of the operators to be the PRIMARY and the other to be 
the SECONDARY.  Route all of the control wiring to the PRIMARY 
operator first.  This will prevent grounding looping problems which can 
occur when more than one COMMON or ground wire is attached 
between separate operators. All accessory equipment should also be 
wired to the PRIMARY.    

 

 

From each of the control inputs with accessory equipment attached, run 
a separate wire to its counterpart terminal on the SECONDARY 
operator .  1/4" disconnect terminals for each command input are 
provided for this purpose.  Use conduit SEPARATE from AC power 
service.   See Figure 14  for the correct wiring.  

 

 

 

FINAL INSTALLATION CHECKLIST 

 

1. Use a voltmeter to assure the  service  voltage  to  the 

operator is 115 VAC.  Connection to 220 VAC service is 
the most common cause of board failure in new 
installations and is NOT COVERED BY WARRANTY! 

 
2. No accessory equipment is installed in the control box. 
3. All wires attached to the 11 position terminal strip or 

the 3-terminal connector on the control box are well 
clear of the motor V-belt and the limit switches. 

 
4. The junction box cover is securely fastened . 

 

RISK OF ENTRAPMENT. 

THE OVERLOAD POTENTIOMETER MUST BE 

SET MORE PRECISELY PRIOR TO COMPLETING 

THE OPERATOR INSTALLATION  

    W A R N I N G !  

RISK OF ELECTROCUTION 

DO NOT BEGIN TO SET THE FOLLOWING 

ADJUSTMENTS  UNTIL THE POWER IS TURNED 

OFF AT THE LEADER CONTROL BOX 

    W A R N I N G !  

 D

: STARTING THE OPERATOR  

Figure 18:  Setting the Limits 

Figure 18:  Setting Limits - Left Hand Installation 

104895 

Содержание HDSLG 1000

Страница 1: ...date of manufacture meets all ANSI UL 325 Safety Requirements for Vehicular gate operators HDSLG 1000 Heavy Duty Vehicular Slide Gate Operator READ THIS MANUAL CAREFULLY BEFORE INSTALLATION OR USE Se...

Страница 2: ...rator Lock 19 Maximum Run Timer 19 Final Setting for Bi Parting Installations 19 Fuses 20 Section E Auxiliary Equipment 20 Section F Safety Guide 21 Operator Exploded View Parts List 23 Technical Spec...

Страница 3: ...LG built in overload detector will activate if there is an abrupt increase in motor current above that normally required to move the gate THE OVERLOAD DETECTION POINT IS AN ADJUSTABLE SETTING THAT MUS...

Страница 4: ...gn to protect system entrapment zones Allstar can provide these products for incorporation in your gate installation CANTILEVERED ROLLER GATES WITH OPEN ROLLERS HAVE THE POTENTIAL HAZARD OF HANDS AND...

Страница 5: ...ct any auxiliary equipment to the operator detectors card readers etc until the gate operator and all its functions are fully tested Only connect one device at a time and ensure its proper function s...

Страница 6: ...ide of the operator Four redhead bolts 3 8 or 1 2 in diameter should be used for mounting the operator The bolt pattern is 10 wide by 16 3 4 long The two rear bolts closest to the gate should be no cl...

Страница 7: ...to determine the correct wire size The NOMINAL column is the ideal distance from the breaker panel to the operator for a given wire size The distances shown in the MAXIMUM column should never be excee...

Страница 8: ...of the slot 8 above the top of the operator pad Attach one end of the chain to the gate and thread the other end through the idler pulleys and drive sprocket Attach the free end to the bracket on the...

Страница 9: ...et failure With the operator properly aligned with the gate drill the remaining three holes with the operator in place Before inserting the remaining redhead bolts make sure the operator is sitting le...

Страница 10: ...lightning strike be shunted to ground This must be done without raising the potential of the circuitry in the operator with respect to ground to the levels that will damage the solid state circuitry L...

Страница 11: ...cturer s instructions Crimp 1 4 quick disconnect lugs to the RELAY COMMON and PRESENCE OUTPUT wires on the detector harness The RELAY COMMON wire is connected to terminal 1 COMMON on the control box 1...

Страница 12: ...ceiver in most cases Many other auxiliary devices such as card readers and key pads using bridge rectifiers require that both sides of the transformer supplying power be floating and not grounded Fail...

Страница 13: ...13 Figure 15 Schematic Wiring Diagram 107788 C INSTALLING THE OPERATOR...

Страница 14: ...vated the gate will not move Gate will move briefly if RADIO or PULSE is activated Gate will run open if HOLD OPEN is activated 7 ALTERNATE Pulsed signal This input is used for COMMAND OPEN COMMAND CL...

Страница 15: ...y connect the receiver For any 4 wire receiver two of the wires will be for power input and two will be for the relay contacts Locate the AUXILIARY Transformer on the Limit Plate Connect the two wires...

Страница 16: ...when more than one COMMON or ground wire is attached between separate operators All accessory equipment should also be wired to the PRIMARY From each of the control inputs with accessory equipment att...

Страница 17: ...TECTION Switch 1 OFF Open Direction The gate will stop move in the close direction for 1 2 second and park Close Direction The gate will stop move in the open direction for 1 2 second and park SWITCH...

Страница 18: ...ed above EXCEPT NOTE that the Open and Close limit switches are REVERSED SETTING THE OBSTRUCTION DETECTION SENSITIVITY T h e operator is equipped with an obstruction detection circuit which will detec...

Страница 19: ...MUM RUN TIMER MRT The control board has a non adjustable maximum run timer circuit The MRT is preset to approximately 45 seconds maximum run time at the factory If the operator initiates an OPEN or CL...

Страница 20: ...close Remove the plate from the loop and observe that the gate closes Some vehicle detectors will tune out a constant obstruction to the loop after 15 to 30 minutes 3 Installing other entry devices Af...

Страница 21: ...n your gate system install the following safety features Electric gate edges Enclosed tracks Vertical guard posts Protective screen mesh Photoelectric sensors Instructional and precautionary signs Cov...

Страница 22: ...be out of reach of the gate so that no one pushing the button or inserting the card is in the path of the gate or moving parts it must also be within INSTALL SAFETY DEVICES In residential application...

Страница 23: ...y Timing Belt 9 54 PD 60 GR 1 ea 20 102832 Cover Control Box HDSLG 1 ea 11 010605 Shaft Lower HDSLG 1 ea 21 102828 Control Box HDSLG 1 ea 12 010198 Bushing Taper Lock 3 4 Bore 1 ea 22 107786 Motor Con...

Страница 24: ...mily home use and two 2 years from the date of purchase for multi family and commercial use To obtain service contact your dealer To obtain service under this warranty the buyer must obtain authorizat...

Отзывы: