ACCESSORY EQUIPMENT HOOK-UP 

 

 
All accessory equipment is hooked-up to the 11 position terminal strip 
located in the control box. See Figure 11.  NO ACCESSORY 
EQUIPMENT SHOULD BE INSTALLED IN THE CONTROL BOX!   
 
 
If local electrical codes permit, use the operator's bottom plate for 
mounting accessory components.  Otherwise, install the accessory 
equipment in an appropriate electrical box. 
 
 
 
The command inputs for the operator require a switch closure to 
COMMON of less than 100 OHMS resistance and for more than 100 
milliseconds duration.  The inputs - HOLD OPEN, REVERSING &  
STOP - can be continuous signals.  A label on the control box lists the 
function of each of the terminals on the barrier strip.  See the Reference 
Chart on Page 14. 
 
 

WIRING VEHICLE DETECTORS 

 

Place the detector on the bottom plate of the frame or in a remote 
electrical box, NEVER in the control box. Hook-up the power and loop 
wires on the detector harness according to the manufacturer's 
instructions.  Crimp 1/4" quick disconnect lugs to the RELAY 
COMMON and PRESENCE OUTPUT wires on the detector harness.  
The RELAY COMMON wire is connected to terminal #1, COMMON, 
on the control box 11 position terminal strip.  The PRESENCE 
OUTPUT wire is connected to terminal #8, REVERSING.  See Figure 
10,  for a typical installation. 
 
 
 
Set the detector frequency and sensitivity switches on the detector 
according to the manufacturer's instructions. 
 
 

 
WIRING FREE EXIT DETECTORS 

 

The installation of a free exit loop detector is identical to 
a vehicle loop detector with the following exceptions:  
Connect the PRESENCE OUTPUT wire of the detector 
wiring harness to terminal #2, HOLD OPEN, on the 
terminal strip.  The RELAY COMMON wire is 
connected to terminal #1. 
 

 
 

C

: INSTALLING THE OPERATOR  

Figure 11:  Wiring a 3-Wire Receiver 

104890 

F

igure 12:  Wiring a 4-Wire Receiver 

104891 

RISK OF ENTRAPMENT! 

TO REDUCE THE RISK OF INJURY OR DEATH:   

LOCATE KEYPAD, CARD READER, KEY 

SWITCH OR SIMILAR ENTRY DEVICES IN A 

LOCATION WHERE A USER CAN NOT REACH 

THROUGH THE GATE OR FENCE TO ACTIVATE 

THE GATE OPERATOR.  THE RECOMMENDED 

DISTANCE BETWEEN THE GATE OR FENCE 

 

WARNING! 

 

Содержание HDSLG 1000

Страница 1: ...date of manufacture meets all ANSI UL 325 Safety Requirements for Vehicular gate operators HDSLG 1000 Heavy Duty Vehicular Slide Gate Operator READ THIS MANUAL CAREFULLY BEFORE INSTALLATION OR USE Se...

Страница 2: ...rator Lock 19 Maximum Run Timer 19 Final Setting for Bi Parting Installations 19 Fuses 20 Section E Auxiliary Equipment 20 Section F Safety Guide 21 Operator Exploded View Parts List 23 Technical Spec...

Страница 3: ...LG built in overload detector will activate if there is an abrupt increase in motor current above that normally required to move the gate THE OVERLOAD DETECTION POINT IS AN ADJUSTABLE SETTING THAT MUS...

Страница 4: ...gn to protect system entrapment zones Allstar can provide these products for incorporation in your gate installation CANTILEVERED ROLLER GATES WITH OPEN ROLLERS HAVE THE POTENTIAL HAZARD OF HANDS AND...

Страница 5: ...ct any auxiliary equipment to the operator detectors card readers etc until the gate operator and all its functions are fully tested Only connect one device at a time and ensure its proper function s...

Страница 6: ...ide of the operator Four redhead bolts 3 8 or 1 2 in diameter should be used for mounting the operator The bolt pattern is 10 wide by 16 3 4 long The two rear bolts closest to the gate should be no cl...

Страница 7: ...to determine the correct wire size The NOMINAL column is the ideal distance from the breaker panel to the operator for a given wire size The distances shown in the MAXIMUM column should never be excee...

Страница 8: ...of the slot 8 above the top of the operator pad Attach one end of the chain to the gate and thread the other end through the idler pulleys and drive sprocket Attach the free end to the bracket on the...

Страница 9: ...et failure With the operator properly aligned with the gate drill the remaining three holes with the operator in place Before inserting the remaining redhead bolts make sure the operator is sitting le...

Страница 10: ...lightning strike be shunted to ground This must be done without raising the potential of the circuitry in the operator with respect to ground to the levels that will damage the solid state circuitry L...

Страница 11: ...cturer s instructions Crimp 1 4 quick disconnect lugs to the RELAY COMMON and PRESENCE OUTPUT wires on the detector harness The RELAY COMMON wire is connected to terminal 1 COMMON on the control box 1...

Страница 12: ...ceiver in most cases Many other auxiliary devices such as card readers and key pads using bridge rectifiers require that both sides of the transformer supplying power be floating and not grounded Fail...

Страница 13: ...13 Figure 15 Schematic Wiring Diagram 107788 C INSTALLING THE OPERATOR...

Страница 14: ...vated the gate will not move Gate will move briefly if RADIO or PULSE is activated Gate will run open if HOLD OPEN is activated 7 ALTERNATE Pulsed signal This input is used for COMMAND OPEN COMMAND CL...

Страница 15: ...y connect the receiver For any 4 wire receiver two of the wires will be for power input and two will be for the relay contacts Locate the AUXILIARY Transformer on the Limit Plate Connect the two wires...

Страница 16: ...when more than one COMMON or ground wire is attached between separate operators All accessory equipment should also be wired to the PRIMARY From each of the control inputs with accessory equipment att...

Страница 17: ...TECTION Switch 1 OFF Open Direction The gate will stop move in the close direction for 1 2 second and park Close Direction The gate will stop move in the open direction for 1 2 second and park SWITCH...

Страница 18: ...ed above EXCEPT NOTE that the Open and Close limit switches are REVERSED SETTING THE OBSTRUCTION DETECTION SENSITIVITY T h e operator is equipped with an obstruction detection circuit which will detec...

Страница 19: ...MUM RUN TIMER MRT The control board has a non adjustable maximum run timer circuit The MRT is preset to approximately 45 seconds maximum run time at the factory If the operator initiates an OPEN or CL...

Страница 20: ...close Remove the plate from the loop and observe that the gate closes Some vehicle detectors will tune out a constant obstruction to the loop after 15 to 30 minutes 3 Installing other entry devices Af...

Страница 21: ...n your gate system install the following safety features Electric gate edges Enclosed tracks Vertical guard posts Protective screen mesh Photoelectric sensors Instructional and precautionary signs Cov...

Страница 22: ...be out of reach of the gate so that no one pushing the button or inserting the card is in the path of the gate or moving parts it must also be within INSTALL SAFETY DEVICES In residential application...

Страница 23: ...y Timing Belt 9 54 PD 60 GR 1 ea 20 102832 Cover Control Box HDSLG 1 ea 11 010605 Shaft Lower HDSLG 1 ea 21 102828 Control Box HDSLG 1 ea 12 010198 Bushing Taper Lock 3 4 Bore 1 ea 22 107786 Motor Con...

Страница 24: ...mily home use and two 2 years from the date of purchase for multi family and commercial use To obtain service contact your dealer To obtain service under this warranty the buyer must obtain authorizat...

Отзывы: