507276-03
Page 31 of 59
Issue 1621
Figure 39
C
A
E
D
B
A
B
D
D
B
C
A
C
12"
1
1
2
2
2" (51 mm)
Vent Pipe
3" (76 mm)
Vent Pipe
A
− Clearance above
grade or average snow
accumulation
B
−Horizontal
separation between
intake and exhaust
C
−Minimum from
end of exhaust to
inlet of intake
D
−Exhaust pipe length
E
−Wall support distance
from top of each pipe
(intake/exhaust)
12" (508 mm) Min.
12" (508 mm) Min.
6" (152 mm) Min.
24" (610 mm) Max
9" (227 mm) Min.
12" (305 mm) Min.
16" (405 mm) Max.
6" (152 mm) Max.
6" (152 mm) Min.
24" (610 mm) Max
9" (227 mm) Min.
12" (305 mm) Min.
20" (508 mm) Max.
6" (152 mm) Max.
TABLE 9
1
The exhaust termination tee should be connected to the 2" or 3" PVC flue pipe as shown in the illustration. Do
not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.
2
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield (24 inches
square) should be used to protect the wall surface. If optional tee is used, the protective shield is recom-
mended. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints,
cracks, etc. in affected area, should be sealed using an appropriate sealant.
3
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away
from adjacent property. The exhaust must never be directed toward the combustion air inlet.
NOTE
− See unit installation instructions for proper exhaust pipe termination size reduction.
Front View of
Intake and Exhaust
Intake
Exhaust
3
Intake
Exhaust
Содержание 95G1UHE
Страница 3: ...507276 03 Page 3 of 59 Issue 1621 EXPANDED VIEW Figure 1 ...
Страница 22: ...507276 03 Page 22 of 59 Issue 1621 Figure 25 Figure 26 ...
Страница 28: ...507276 03 Page 28 of 59 Issue 1621 Figure 34 ...
Страница 38: ...507276 03 Page 38 of 59 Issue 1621 Figure 57 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC ...
Страница 40: ...507276 03 Page 40 of 59 Issue 1621 Figure 59 Figure 60 ...
Страница 44: ...507276 03 Page 44 of 59 Issue 1621 TYPICAL WIRING DIAGRAM Figure 65 ...
Страница 57: ...507276 03 Page 57 of 59 Issue 1621 Start Up Performance Check List ...