304
Command Reference for IE200 Series Industrial Managed PoE+ Switches
C613-50066-01 REV A
AlliedWare Plus™ Operating System - Version 5.4.5I-0.x
A
LARM
M
ONITORING
C
OMMANDS
ALARM
FACILITY
alarm facility
Overview
Use this command to enable alarm monitoring. Alarm monitoring is
user-configured, including which alarms are enabled, and the LED and relay
settings for each alarm.
Use the
no
variant of this command to disable the alarm facility for a particular
alarm.
The command syntax varies depending on the type of alarm you are configuring.
The section below includes the syntax for each alarm type.
Syntax
alarm facility epsr {led|relay}
alarm facility input-alarm
<input-alarm-number>
{alarm-position
{open|close}|led|relay}
alarm facility link-down
<port-list>
{led|relay}
alarm facility loopprot {led|relay}
alarm facility main-pse {led|relay}
alarm facility power-supply
<power-supply-number>
{led|relay}
alarm facility pse-port
<port-list>
{led|relay}
alarm facility temperature {led|relay}
no alarm facility {epsr|input-alarm
<number>
|link-aggregation
{partial-failure|total-failure}|link-down
<port-list>
|loopprot|main-pse|power-supply
<id>
|pse-port
<port-list>
|temperature} {led|relay}
Parameter
Description
epsr
EPSR alarm
input-alarm
External contact input alarm.
<input-alarm-number>
The external contact input number. The current
models have only a single pair of input contacts, so
this number must be 1.
link-down
Link failure alarm. A link is down on a particular switch
port.
<port-list>
The switch ports on which the alarm will be activated
or disabled. The port list can be any of the following:
•
An individual port. Example: 1.0.3
•
A continuous range of ports. Example: 1.0.1-1.0.3
•
A combination of individual ports and port ranges,
separated by commas. Example: 1.0.1, 1.0.3-1.0.4
loopprot
Loop protection alarm.