Connection Specifications
IMPORTANT: Connection must be made by a qualified
electrician using wiring diagram provided with ma-
chine, or according to accepted European Union stand-
ards.
Connect machine to an individual branch circuit not shared with
lighting or other equipment. Shield connection in a liquid-tight or
approved flexible conduit. Copper conductors of correct size
must be installed in accordance with National Electric Code
(NEC) or other applicable codes.
Use wire sizes indicated in the Electrical Specifications chart for
runs up to 50 feet [15 m]. Use next larger size for runs of 50 to
100 feet [15 to 30 m]. Use two (2) sizes larger for runs greater
than 100 feet [30 m].
Single Phase Connection
Connect the electrical service's wires to the machine's electrical
connection terminal as shown.
Electrical Service Wire
Machine's Electrical
Connection Terminal
U
U
Neutral
N
PE
PE (Ground)
Table 13
Electrical Connection Terminal Block
N
CHM2499N_SVG
Figure 23
Single-Phase Connection
PE
U N
PE
N
U
CHM2500N_SVG
Figure 24
Three Phase Connection
Connect the electrical service's wires to the machine's electrical
connection terminal as shown.
Electrical Service Wire
Machine's Electrical
Connection Terminal
U
U
V
V
W
W
PE
PE (Ground)
Table 14
Electrical Connection Terminal Block
V
W
N
CHM2501N_SVG
Figure 25
Installation
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
39
Part No. D1634ENR4