Supply Cable
The supply cable is not delivered with the machine. The supply
cable must have the following specifications:
• Conductors with copper cores (For wire size details, refer to
Electrical Specifications
)
• Stranded conductors (flexible wiring) that can withstand vi-
bration from machine
• For crossection size, refer to
Table 11 Determining AWG Sizes
• Route the supply cable as short as possible, directly from the
supply protection device to the washer without branching off
• Do not use a plug or extensions cords (the machine is inten-
ded to be permanently connected to the electrical network)
Power supply protection device nominal current (US)
Min. phase conductor
section, AWG [mm
2
]
Min. protection conduc-
tor section, AWG [mm
2
]
Automatic circuit break-
ers
Fuses
16A (15A)
10A (10A)
15 [1.5]
15 [1.5]
20A (20A)
16A (15A)
13 [2.5]
13 [2.5]
25A (-)
20A (20A)
11 [4]
11 [4]
40A (40A)
32A (30A)
9 [6]
9 [6]
63A (-)
50A (50A)
7 [10]
7 [10]
80A
63A
5 [16]
5 [16]
100A
80A
3 [25]
5 [16]
125A
100A
2 [35]
3 [25]
Table 11 Determining AWG Sizes
To connect the supply cable, the following steps must be per-
formed:
1.
Insert cable through opening on rear panel. Insure a strain re-
lief is used so the supply cable can not move.
2.
Strip the conductor ends. Refer to
Figure 21
. The protection
conductor must be longer so it can be routed to the machine
without tension.
CHM2487N_SVG
7
6
5
4
3
2
1
1.
Protection conductor
2.
Phase conductor
3.
Phase conductor
4.
Phase conductor
5.
Neutral conductor
6.
Molded tube
7.
Stripped length of conductors
Figure 21
3.
With stranded conductors, use wire end tubes with an insula-
ted sleeve (6) for L1/U, (L2/V), (L3/W), (N) conductors.
Make sure there is no accidental contact, since the supply ca-
ble stays under voltage even when the main switch is off.
Installation
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
35
Part No. D1634ENR4