14
Rockwell Automation Publication 2711R-UM001E-EN-E - January 2017
Chapter 1
Overview
How to Connect Browser
The terminals can be connected to a browser using an Ethernet network
connection. You must enter the IP address of the PanelView 800 terminal into
the address field of your browser. You can find the IP address on the terminal
configuration screen under Communications.
USB Device Port
The PanelView 800 terminals have a USB device port to support communication
with the terminal using TCP/IP.
Ethernet Port
The PanelView 800 terminals have an Ethernet port. The Ethernet port supports
both static IP addresses and Dynamic Host Configuration Protocol (DHCP)
assigned IP addresses. If using static IP addressing, then you manually set the IP
address, the subnet mask, and the default gateway. If using DHCP, then the
server automatically assigns an IP address, the subnet mask, the default gateway,
and the DNS and WINS server.
IMPORTANT
The web browser feature is only supported on PanelView 800
terminals with firmware revision 2.020 or earlier. It is not supported
from firmware revision 3.011 onwards.
IMPORTANT
The USB device port is for maintenance only and is not intended for
normal run-time operation.
The USB device port is not intended for Customer use.
IMPORTANT
If a terminal is set for DHCP and is not on a network or is on a network
that does not have a DHCP server (or the server is not available), it will
automatically assign itself an Automatic Private IP Address (or auto IP
address). The auto IP address will be in the range of 169.254.0.0 through
169.254.255.255.
The terminal makes sure the auto IP address is unique from any other
auto IP address of other devices on the network. The terminal can now
communicate with other devices on the network that have IP addresses
in the 169.254.xxx.xxx range (and a subnet mask of 255.255.0.0).
Содержание PanelView 800 2711R-T10T
Страница 1: ...User Manual PanelView 800 HMI Terminals Catalog Numbers 2711R T4T 2711R T7T 2711R T10T...
Страница 4: ...4 Rockwell Automation Publication 2711R UM001E EN E January 2017 Summary of Changes Notes...
Страница 8: ...8 Rockwell Automation Publication 2711R UM001E EN E January 2017 Table of Contents Notes...
Страница 88: ...88 Rockwell Automation Publication 2711R UM001E EN E January 2017 Chapter 5 Upgrade Firmware Notes...
Страница 98: ...98 Rockwell Automation Publication 2711R UM001E EN E January 2017 Chapter 7 Recipes Notes...
Страница 118: ...118 Rockwell Automation Publication 2711R UM001E EN E January 2017 Appendix A Specifications Notes...
Страница 142: ...142 Rockwell Automation Publication 2711R UM001E EN E January 2017 Appendix D Configure Security Notes...
Страница 156: ...156 Rockwell Automation Publication 2711R UM001E EN E January 2017 Index Notes...
Страница 157: ......