Rockwell Automation Publication 2711R-UM001E-EN-E - January 2017
101
Troubleshoot the System
Chapter
8
Communication
8
Communication Server Error
Contact technical support providing this data.
ID1-/*S:0 Param1*/, ID2-/*S:0 Param2*/, P1-/*S:0
Param3*/, P2-/*S:0 Param4*/, P3-/*S:0 Param5*/,
P4-/*S:0 Param6*/, P5-/*S:0 Param7*/, P6-/*S:0
Param8*/
Reboot the terminal.
Communication
9
Communication Server Error
Contact technical support providing this data.
ID1-/*S:0 Param1*/, ID2-/*S:0 Param2*/
Reboot the terminal.
Communication
10
Write Error for Alias /*S:0 Param2*/, Controller
/*S:0 Param3*/, Address is /*S:0 Param4*/,
Communication Flag is /*S:0 Param1*/
The terminal is having trouble writing the external
tag at this controller and address.
Verify you have good communication to the
controller.
Verify that the communication network cable is
connected.
If new ladder logic is downloading to the controller,
you could see this message. After the download,
communication should run normally.
If a remote device not responding alert is present,
then all external tags being written to will generate
this alert.
Is the address configured in the controller? If the
address is configured as read only at the controller,
this address can not be written to. Set this external
tag as read and remove panel devices from your
application that can write data to this external tag.
Communication
11
Read Error for Alias /*S:0 Param2*/, Controller
/*S:0 Param3*/, Address is /*S:0 Param4*/,
Communication Flag is /*S:0 Param1*/
The terminal is having trouble reading the
external tag at this controller and address.
Verify you have good communication to the
controller.
Verify that the communication network cable is
connected.
If new ladder logic is downloading to the controller,
you could see this message. After the download,
communication should run normally.
If a remote device not responding alert was present,
then all external tags being read from will generate
this alert.
Is the address configured in the controller? If the
address is configured as write only at the controller,
this address can not be read from. Set this external
tag as write and remove panel devices from your
application that can read data from this external
tag.
PanelView 800 Terminal Alerts
Category
ID
Description
Corrective Action
Содержание PanelView 800 2711R-T10T
Страница 1: ...User Manual PanelView 800 HMI Terminals Catalog Numbers 2711R T4T 2711R T7T 2711R T10T...
Страница 4: ...4 Rockwell Automation Publication 2711R UM001E EN E January 2017 Summary of Changes Notes...
Страница 8: ...8 Rockwell Automation Publication 2711R UM001E EN E January 2017 Table of Contents Notes...
Страница 88: ...88 Rockwell Automation Publication 2711R UM001E EN E January 2017 Chapter 5 Upgrade Firmware Notes...
Страница 98: ...98 Rockwell Automation Publication 2711R UM001E EN E January 2017 Chapter 7 Recipes Notes...
Страница 118: ...118 Rockwell Automation Publication 2711R UM001E EN E January 2017 Appendix A Specifications Notes...
Страница 142: ...142 Rockwell Automation Publication 2711R UM001E EN E January 2017 Appendix D Configure Security Notes...
Страница 156: ...156 Rockwell Automation Publication 2711R UM001E EN E January 2017 Index Notes...
Страница 157: ......