102
Rockwell Automation Publication 2711R-UM001E-EN-E - January 2017
Chapter 8
Troubleshoot the System
Communication
27
Remote Device /*S:0 Param1*/ is Not
Responding
Verify all network connections are correct.
Verify that the communication network cable is
connected.
If new ladder logic is downloading to the controller,
you could see this message. After the download,
communication should run normally.
Verify that the network address of the controller
matches the terminal controller address configured
in the Communication tab.
In the Communication tab, verify that the protocol
specifications are correct, such as communication
rate, data bits, stop bits. These are all protocol
specific.
Communication
28
Invalid Data Address /*S:0 Param1*/
This is not syntactically a valid address.
Communication
30
Bad address in block /*S:0 Param1*/ to /*S:0
Param2*/ on device /*S:0 Param3*/
This can occur when a write only address for a
controller has been set for read/write in the external
tag of the terminal. Param1 to Param2 specifies the
address block having the issue. Somewhere within
the range is where the write only address is defined
in a PanelView external tag. Set the external tag to
write.
Recipe
1001 Recipe upload started.
This message is for informational purposes. No
corrective action needed.
Recipe
1002 Recipe save failed. Cause: Recipe in Table has not
been modified.
Make sure that the recipe table is modified before
the save operation is done.
Recipe
1003 Recipe save had errors.
This message is for informational purposes. No
corrective action needed.
Recipe
1004 Recipe save completed successfully.
This message is for informational purposes. No
corrective action needed.
Recipe
1005 Recipe download failed. Cause: Operation
cancelled.
This message is for informational purposes. No
corrective action needed.
Recipe
1006 Recipe download started.
This message is for informational purposes. No
corrective action needed.
Recipe
1007 Recipe download completed with errors.
This message is for informational purposes. No
corrective action needed.
Recipe
1008 Recipe download completed successfully.
This message is for informational purposes. No
corrective action needed.
PanelView 800 Terminal Alerts
Category
ID
Description
Corrective Action
Содержание PanelView 800 2711R-T10T
Страница 1: ...User Manual PanelView 800 HMI Terminals Catalog Numbers 2711R T4T 2711R T7T 2711R T10T...
Страница 4: ...4 Rockwell Automation Publication 2711R UM001E EN E January 2017 Summary of Changes Notes...
Страница 8: ...8 Rockwell Automation Publication 2711R UM001E EN E January 2017 Table of Contents Notes...
Страница 88: ...88 Rockwell Automation Publication 2711R UM001E EN E January 2017 Chapter 5 Upgrade Firmware Notes...
Страница 98: ...98 Rockwell Automation Publication 2711R UM001E EN E January 2017 Chapter 7 Recipes Notes...
Страница 118: ...118 Rockwell Automation Publication 2711R UM001E EN E January 2017 Appendix A Specifications Notes...
Страница 142: ...142 Rockwell Automation Publication 2711R UM001E EN E January 2017 Appendix D Configure Security Notes...
Страница 156: ...156 Rockwell Automation Publication 2711R UM001E EN E January 2017 Index Notes...
Страница 157: ......