1761-6.5
5-2
DNI Configuration Parameters and Programming Notes
EDS Parameters for the DNI
The following list shows the available parameters for configuring the DNI.
Parameter definitions and usage information are provided in the sections
following the table.
Important:
When modifying most DNI parameters, you must first disable polling (Set
the Data Enable parameter to disable for DNI Series A. Set the I/O Scan
Enable parameter to disable for DNI Series B). You can enable polling after
setting your configuration. For information on how to set up and modify
parameters, see "Setup, Programming, and Troubleshooting" on page 6-1.
Parameter
Type
Parameter Number
Description
Range
Default Value
For More
Information
Series A Series B
I/O
4
1
Input Size
Series A: 1 to 16
Series B: 1 to 32
1 word
I/O
Not
Applicable
2
Input Split Point
1 to 32
1 word
I/O
5
3
Input Type
Bit or Integer File
Integer File
I/O
6
4
Input Data File
3 to 254
7
I/O
7
5
Input Word Offset
0 to 254
0
I/O
8
6
Output Size
Series A: 1 to 16
Series B: 1 to 32
1 word
I/O
Not
Applicable
7
Output Split Point
1 to 32
1 word
I/O
9
8
Output Type
Bit or Integer File
Integer File
I/O
10
9
Output Data File
3 to 254
7
I/O
11
10
Output Word Offset
0 to 254
1
I/O
14
11
DF1 Device
0 to 3:
0: Other
1: PLC
2: SLC/ Other MicroLogix
3: MicroLogix 1000
3 = MicroLogix 1000 5-13
I/O
3
12
DNI Series A: Data Enable
DNI Series B: I/O Scan Enable
(Polling Enable)
Disabled (0) or Enabled (1)
Disabled (0)
I/O
12
13
DF1 Heartbeat
Series A: 2 to 10
Series B: 1 to 10
2
I/O
13
14
Data Scan Delay
(Polling Delay)
20 to 3000 ms
50 ms
Messaging 2
15
Message Timeout
0 to 2500 ms
0 ms
Messaging
Not
Applicable
16
DF1 Substitute Address
0 to 64
64 = Disabled
DF1
15
17
DF1 Autobaud
Disabled (0) or Enabled (1)
Enabled (1)
DF1
16
18
DF1 Baud Rate
0 to 5:
0: 38,400
1: 19,200
2: 9600
3: 4800
4: 2400
5: 1200
Series A: 2 = 9600
Series B: 1 = 19,200
DeviceNet 1
19
DeviceNet Autobaud
Disabled (0) or Enabled (1)
Enabled (1)
Device
17
Not
Applicable
DNI Mode
Standby (0) or Operational ( 1) Operational (1)
Содержание DeviceNet 1761-NET-DNI
Страница 14: ...1761 6 5 P 6...
Страница 16: ...1761 6 5 1 2 Product Overview...
Страница 22: ...1761 6 5 2 6 Quick Start for Experienced Users...
Страница 34: ...1761 6 5 4 6 Installation and Wiring...
Страница 74: ...1761 6 5 6 16 Setup Programming and T roubleshootin g...
Страница 84: ...1761 6 5 7 10 Application Examples...
Страница 94: ...1769 6 5 A 4 Specifications...
Страница 99: ...1761 6 5 I 3 AB Parts...
Страница 100: ......