1761-6.5
6-10
Setup, Programming, and Troubleshootin g
Troubleshooting
LED Indicators
The DeviceNet Interface has three LED indicators:
MOD LED (Module Status LED)
The module status LED provides information specific to the DNI.
LED
Color
Module Status LED
bicolor - red/green
Network Status LED
bicolor - red/green
RS-232 LED
green
LED Condition
DNI State
Problem/Indication
Off
Not Powered
The device may not be powered or
firmware unable to run.
Green
(1)
(1) Normal condition.
•
DNI Series A: Device
Operational
•
DNI Series B:
Device Scanning
The device is operating in a normal
condition.
Flashing Green
(1)
•
DNI Series A:
Device in Standby
•
DNI Series B:
Device Not Scanning
•
For DNI Series A only, the device may
be in Standby Mode; set to
operational.
•
For DNI Series B, I/O Scan (Polling
Enable) may need to be set (1).
Flashing Red
Minor Fault
Recoverable fault.
•
DNI may need to be commissioned
(the DNI will not operate when set to
the out-of-box defaults).
•
The device needs commissioning
due to missing, incomplete, or
incorrect configuration.
•
EEPROM may be corrupt,
re-commission the DNI.
Red
Unrecoverable Fault
The device has an unrecoverable fault
which requires the power to be cycled,
or the DNI may need to replaced.
Flashing Red-Green Device Self Testing
The device is in self test and should only
occur at power up or re set.
Содержание DeviceNet 1761-NET-DNI
Страница 14: ...1761 6 5 P 6...
Страница 16: ...1761 6 5 1 2 Product Overview...
Страница 22: ...1761 6 5 2 6 Quick Start for Experienced Users...
Страница 34: ...1761 6 5 4 6 Installation and Wiring...
Страница 74: ...1761 6 5 6 16 Setup Programming and T roubleshootin g...
Страница 84: ...1761 6 5 7 10 Application Examples...
Страница 94: ...1769 6 5 A 4 Specifications...
Страница 99: ...1761 6 5 I 3 AB Parts...
Страница 100: ......