Input Size
This parameter identifies the size, in words, of the data array that is read
from the controller attached to the DNI’s RS-232 port. The array may
contain up to 16 (16-bit) words of data for DNI Series A (32 words for DNI
Series B) from a contiguous block within the attached controller.
The first byte (byte 0) of the first word contains the status byte and is not
available to the user. A sample of the data array is shown below:
Parameter
Type
Parameter Number
Description Range
Default Value
Series A Series B
I/O
4
1
Input Size
Series A: 1 to 16
Series B: 1 to 32
1
Important:
For DNI Series B, you must also configure the Input Split
Point. See page 5-4.
Word
Input Image
Series A Series B
0
0
Data (8 bits)
Status
1
1
Data Most Significant Byte (MSB) Data Least Significant Byte (LSB)
2
2
Data MSB
Data LSB
3
3
Data MSB
Data LSB
↓
↓
↓
↓
14
30
Data MSB
Data LSB
15
31
Data MSB
Data LSB
Note:
Byte 1 (MSB) of word 0 is available for user data.
Note:
For information on the Status Byte (byte 0), see the Status Byte
section on page 5-23.
Содержание DeviceNet 1761-NET-DNI
Страница 14: ...1761 6 5 P 6...
Страница 16: ...1761 6 5 1 2 Product Overview...
Страница 22: ...1761 6 5 2 6 Quick Start for Experienced Users...
Страница 34: ...1761 6 5 4 6 Installation and Wiring...
Страница 74: ...1761 6 5 6 16 Setup Programming and T roubleshootin g...
Страница 84: ...1761 6 5 7 10 Application Examples...
Страница 94: ...1769 6 5 A 4 Specifications...
Страница 99: ...1761 6 5 I 3 AB Parts...
Страница 100: ......