Publication 1756-UM001G-EN-P - January 2007
60
Place, Configure, and Monitor I/O Modules
Address I/O Data
I/O information is presented as a set of tags.
•
Each tag uses a structure of data. The structure depends on the
specific features of the I/O module.
•
The name of the tags is based on the location of the I/O module
in the system.
An I/O address follows this format.
Location
:Slot
:Type
.Member
.SubMember
.Bit
= Optional
Where
Definition
Location
Network location
LOCAL = same chassis or DIN rail as the controller
ADAPTER_NAME
= identifies remote communication adapter or bridge module
Slot
Slot number of I/O module in its chassis or DIN rail
Type
Type of data
I = input
O = output
C = configuration
S = status
Member
Specific data from the I/O module; depends on what type of data the module can store.
•
For a digital module, a Data member usually stores the input or output bit values.
•
For an analog module, a Channel member (CH#) usually stores the data for a channel.
SubMember
Specific data related to a Member.
Bit
Specific point on a digital I/O module; depends on the size of the I/O module (0...31 for a 32-point module)
Содержание controllogix 1756-L55M12
Страница 4: ...Publication 1756 UM001G EN P January 2007 Summary of Changes 4 Notes...
Страница 10: ...Publication 1756 UM001G EN P January 2007 10 Notes...
Страница 20: ...Publication 1756 UM001G EN P January 2007 20 Directly Connect to the Controller via the Serial Port Notes...
Страница 66: ...Publication 1756 UM001G EN P January 2007 66 Place Configure and Monitor I O Modules Notes...
Страница 82: ...Publication 1756 UM001G EN P January 2007 82 Develop Applications Notes...
Страница 122: ...Publication 1756 UM001G EN P January 2007 122 Maintain Nonvolatile Memory Notes...
Страница 130: ...Publication 1756 UM001G EN P January 2007 130 Maintain the Battery Notes...
Страница 134: ...Publication 1756 UM001G EN P January 2007 134 LED Indicators Notes...