Publication 1756-UM001G-EN-P - January 2007
126
Maintain the Battery
Estimate 1756-BA2
Battery Life
(1756-L6
x
series B controllers only)
Use this table to estimate how much time will elapse before the
battery becomes low (BAT LED = solid red) on 1756-L6
x
, series B
controllers.
Worst-case Estimates of 1756-BA2 Battery Life
Worst-case Estimates of 1756-BATM Battery Life
Controller
Temperature
Time Before BAT LED Turns On
Time after BAT LED turns on
and Power Is Cut Off
Power off 100%
Power off 50%
Yearly
decrease
1756-L55M12
1756-L55M13
60 °C (140 °F)
190 days
396 days
11%
190 days
25 °C (77 °F)
299 days
562 days
5%
299 days
0 °C (32 °F)
268 days
562 days
6%
268 days
1756-L55M14
60 °C (140 °F)
130 days
270 days
11%
139 days
25 °C (77 °F)
213 days
391 days
5%
228 days
0 °C (32 °F)
180 days
381 days
6%
193 days
1756-L55M16
60 °C (140 °F)
71 days
160 days
13%
76 days
25 °C (77 °F)
133 days
253 days
5%
142 days
0 °C (32 °F)
105 days
220 days
6%
112 days
1756-L55M22
1756-L55M23
Use the values for the 1756-L55M13 controller.
1756-L55M24
Use the values for the 1756-L55M14 controller.
1756-L63
60 °C (140 °F)
98 days
204 days
11%
104 days
25 °C (77 °F)
146 days
268 days
5%
157 days
0 °C (32 °F)
105 days
222 days
6%
113 days
Temperature 2.54 cm. (1 in.)
Below the Chassis, Max
Power Cycles
Battery Life Before the BAT LED Turns Red
Project Size
1 MB
2 MB
4 MB
8 MB
16 MB
0...40 °C (32...104 °F)
3 per day
3 years
3 years
26 months
20 months
10 months
2 per day or less
3 years
3 years
3 years
31 months
16 months
41...45 °C (105.8...113 °F)
3 per day
2 years
2 years
2 years
20 months
10 months
2 per day or less
2 years
2 years
2 years
2 years
16 months
46...50 °C (114.8...122 °F)
3 per day or less
16 months
16 months
16 months
16 months
10 months
51...55 °C (123.8...131 °F)
3 per day or less
11 months
11 months
11 months
11 months
10 months
56...60 °C (132.8...140 °F)
3 per day or less
8 months
8 months
8 months
8 months
8 months
Содержание controllogix 1756-L55M12
Страница 4: ...Publication 1756 UM001G EN P January 2007 Summary of Changes 4 Notes...
Страница 10: ...Publication 1756 UM001G EN P January 2007 10 Notes...
Страница 20: ...Publication 1756 UM001G EN P January 2007 20 Directly Connect to the Controller via the Serial Port Notes...
Страница 66: ...Publication 1756 UM001G EN P January 2007 66 Place Configure and Monitor I O Modules Notes...
Страница 82: ...Publication 1756 UM001G EN P January 2007 82 Develop Applications Notes...
Страница 122: ...Publication 1756 UM001G EN P January 2007 122 Maintain Nonvolatile Memory Notes...
Страница 130: ...Publication 1756 UM001G EN P January 2007 130 Maintain the Battery Notes...
Страница 134: ...Publication 1756 UM001G EN P January 2007 134 LED Indicators Notes...