Publication 1756-UM001G-EN-P - January 2007
116
Configure Redundancy
Redundancy and Scan Time
The primary controller stops at the end of every program to crossload
fresh data to the secondary controller. This keeps the secondary
controller up-to-date and ready to take over. It also increases the scan
time when compared to a nonredundant system.
The amount of time a crossload consumes depends on how much
data the primary controller has to crossload:.
•
The primary controller crossloads any tag to which an
instruction wrote a value, even the same value, since the last
crossload.
•
Crossloading also requires a small amount of overhead time to
tell the secondary controller which program the primary
controller is executing.
Minimum System
Requirements
At a minimum, a ControlLogix redundancy system must contain these
items.
Quantity
Item
Notes
2
ControlLogix chassis
Both chassis must be the same size.
2
ControlLogix power supply
2
ControlLogix controller
•
Use either 1756-L55, 1756-L61, 1756-L62, 1756-L63,
or 1756-L64 controllers.
•
Use the same catalog number and memory size
controllers in each chassis.
2
ControlLogix ControlNet
communication module
Use series D modules.
2
ControlLogix 10/100 Mbps
Ethernet/IP communication module
•
Optional
•
You can use a second pair of 1756 ControlNet
communication modules for HMI/workstation
communication.
2
1757 system redundancy module
1
1757 system redundancy cable
Standard lengths are available.
2
Additional ControlNet nodes
•
Place all I/O in remote chassis or din rails.
•
Use a ControlNet network for all I/O.
•
Add at least 2 nodes to each ControlNet network in
addition to the redundant chassis pair.
Содержание controllogix 1756-L55M12
Страница 4: ...Publication 1756 UM001G EN P January 2007 Summary of Changes 4 Notes...
Страница 10: ...Publication 1756 UM001G EN P January 2007 10 Notes...
Страница 20: ...Publication 1756 UM001G EN P January 2007 20 Directly Connect to the Controller via the Serial Port Notes...
Страница 66: ...Publication 1756 UM001G EN P January 2007 66 Place Configure and Monitor I O Modules Notes...
Страница 82: ...Publication 1756 UM001G EN P January 2007 82 Develop Applications Notes...
Страница 122: ...Publication 1756 UM001G EN P January 2007 122 Maintain Nonvolatile Memory Notes...
Страница 130: ...Publication 1756 UM001G EN P January 2007 130 Maintain the Battery Notes...
Страница 134: ...Publication 1756 UM001G EN P January 2007 134 LED Indicators Notes...