Publication 1756-UM001G-EN-P - January 2007
40
Communicate over Networks
Click the System Protocol tab.
5.
Specify system protocol settings.
The station address specifies the node address of the controller
on the DH-485 network.
a. From the Station Address pull-down menu, choose a station
address number from 1...31, decimal.
To optimize network performance, assign station addresses in
sequential order.
Assign initiators, such as personal computers, the lowest
station address numbers to minimize the time required to
initialize the network.
The maximum station address specifies the maximum node
address of all the devices on the DH-485 network.
b. From the Max Station Address pull-down menu, choose a
maximum station address number from 1...31, decimal.
To optimize network performance, make sure:
•
the maximum station address is the highest node number
being used on the network.
•
that all the devices on the same DH-485 network have the
same selection for the maximum station address.
The token hold factor is the number of transmissions (plus
retries) that an address holding a token can send onto the data
link each time that it receives the token.
Содержание controllogix 1756-L55M12
Страница 4: ...Publication 1756 UM001G EN P January 2007 Summary of Changes 4 Notes...
Страница 10: ...Publication 1756 UM001G EN P January 2007 10 Notes...
Страница 20: ...Publication 1756 UM001G EN P January 2007 20 Directly Connect to the Controller via the Serial Port Notes...
Страница 66: ...Publication 1756 UM001G EN P January 2007 66 Place Configure and Monitor I O Modules Notes...
Страница 82: ...Publication 1756 UM001G EN P January 2007 82 Develop Applications Notes...
Страница 122: ...Publication 1756 UM001G EN P January 2007 122 Maintain Nonvolatile Memory Notes...
Страница 130: ...Publication 1756 UM001G EN P January 2007 130 Maintain the Battery Notes...
Страница 134: ...Publication 1756 UM001G EN P January 2007 134 LED Indicators Notes...