Install the QDC Module
Chapter 2
2-4
Table 2.A
Jumper Settings
Jumper
Function
Setting
E1
Run/Calibrate (Appendix G)
Calibrate = right
Run = left [1]
E5
I/O Density
Standard = top [1]
Do not use bottom position
E6
E7
E8
E9
Input 1 (Screw position)
Input 2 (Screw pressure)
Input 3 (Screw RPM)
Input 4 (Cavity pressure)
Voltage = right [1]
Current = left
E10
E14
E13
E17
Output 1 (Valve 1)
Output 2 (Valve 2)
Output 3 (Valve 3)
Output 4 (Valve 4)
Current = top
Voltage = bottom [1]
E11
E12
E15
E16
Output 1 (Valve 1)
Output 2 (Valve 2)
Output 3 (Valve 3)
Output 4 (Valve 4)
-10 to +10VDC = top
0 to +10VDC or
4 to 20mA = bottom [1]
[1] factoryset defaults
Important: If you select current output with jumper plugs E10, E14, E13,
and/or E17, then you must select the 4 to 20mA jumper position with E11,
E12, E15, and/or E16.
ATTENTION: If an output is unconnected, set the jumper
(E11, E12, E15, and/or E16) that corresponds to that output to 0
to 10 Vdc (bottom position). Setting the jumpers for –10 to +10
Vdc and later configuring the output as “unconnected” causes
the QDC module to output –10 Vdc on that channel when
stopped or when a system reset occurs and all outputs are forced
to 0% (i.e. 0% output equals –10Vdc).
Important: Selecting –10 to +10 VDC with jumper E11, E12, E15, and/or
E16 sets the QDC module for bi-directional valve operation. The
relationship to percentage output is as follows:
-10
0
10
0 10 20 30 40 50 60 70 80 90 100
%Output Requested
Output V
oltage (Vdc)