Chapter 27
The Status File
27–33
The figures below are the status file displays that apply to the SLC 5/01 and
fixed processors. The displays are accessible offline and online under the
EDT DAT function. To move between data files: Press NEXT FL or
PREV FL. To move between displays: Press NEXT PG or PREV PG. To
move the cursor from any data file address to any other data file address:
Press ADDRESS, enter the address, then press ENTER.
F1
F2
F3
F4
F5
Status File
Arithmetic Flags S:0 Z:0 V:0 C:0
S2:0 Proc Status 0000 0000 0000 0000
S2:1 Proc Status 0000 0000 1000 0001
S2:2 Proc Status 1000 0000 0000 0010
S2:0/0 = 0 PRG
ADDRESS NEXT FL PREV FL NEXT PG PREV PG
F1
F2
F3
F4
F5
Status File
S2:5 Minor Fault 0000 0000 0000 0000
S2:6 Fault Code 0000H
Desc: No Error
S2:3L Program Scan [x10mS] last: 0
S2:3H Watchdog [x10mS] 10
S2:5/0 = 0 PRG
ADDRESS NEXT FL PREV FL NEXT PG PREV PG
F1
F2
F3
F4
F5
Status File
S2:7 Suspend Code 0
S2:8 Suspend File 0
S2:4 Running Clock 0000 0000 0000 0000
S2:13&14 Math Register 00000000H
S2:7 = 0 PRG
ADDRESS NEXT FL PREV FL NEXT PG PREV PG
F1
F2
F3
F4
F5
Status File
S2:15H Communication KBaud Rate 19.2
S2:15L Processor Address 1
Note:
Enter 3 for 9600
Enter 4 for 19200
S2:15H = 4 PRG
ADDRESS NEXT FL PREV FL NEXT PG PREV PG
F1
F2
F3
F4
F5
Status File
S2:9 & S2:10 Active Node List
1 2 3
0 0 0 0
0111 1000 0000 0000 0000 0000 0000 0000
Node = 0
S2:9/0 = 0 PRG
ADDRESS NEXT FL PREV FL NEXT PG PREV PG
F1
F2
F3
F4
F5
Status File
S2:11 & S2:12 I/O Slot Enables
1 2 3
0 0 0 0
1111 1111 1111 1111 1111 1111 1111 1111
Slot = 0
S2:11/0 = 1 PRG
ADDRESS NEXT FL PREV FL NEXT PG PREV PG
Status File Display - SLC
5/01 and Fixed Processors