Chapter 8
Compiling and Saving a Program
8–2
2. To save this program and continue editing, press
[F4]
, SAVE_CT. To
save this program and exit offline editing, press
[F5]
, SAVE_EX.
If you are using a SLC 5/02 processor, the following display appears:
Compiler Options
F1
F2
F3
F4
F5
TSTRUNG
FUTACC
ACCEPT
OFL
Future Access:
Yes
MODIFY OPTIONS, ACCEPT TO COMPILE
Test Single Rung:
Disable
Index Across Files:
Disallow
File Protection:
Outputs
MODIFY OPTIONS, ACCEPT TO COMPILE OFL
INDXCHK
FILEPRT
Important: The above display appears if you have a SLC 5/02. If you have
a fixed controller or a SLC 5/01 processor only
[F1]
and
[F5]
appear.
Function Key
Description
[
F1
], Future Access - Fixed, SLC 5/01, and SLC
5/02 processors
Toggles between Yes and No. This option allows
you to protect proprietary program data and
algorithms. The protection takes affect only after
the processor file is downloaded to a controller.
[
F2
], Test Single Rung - SLC 5/02 processor
Toggles between Enable and Disable. This
option allows you to execute your program one
rung at a time or a section at a time. Use this
function for debugging purposes.
[
F3
], Index Checks - SLC 5/02 processor
Toggles between Allow and Disallow. This
option allows you to use indexed addressing to
address data table elements outside of the base
address data file.
[
F4
], File Protect - SLC 5/02 processor
Toggles between Outputs, None, and All. This
option allows you to protect your data table files
from external modification by devices on the
DH-485 network.
[
F5
], ACCEPT
Starts the compile.
3. After you have made your selections press