86
Rockwell Automation Publication 1734-UM013C-EN-P - August 2010
Chapter 6
Configure the Module in a GuardLogix Controller
Configure the Safety Tab
Read this for information about how to complete entries when you click the
Safety tab.
1.
From the Module Properties dialog box, click the Safety tab.
2.
Click Advanced.
The Advanced Connection Reaction Time Limit Configuration dialog
box appears.
1756-UM020
.
a. In the Requested Packet Interval (RPI) box, enter the input connection
RPI to support your application (between 6 and 500 ms).
a
b