126
Rockwell Automation Publication 1734-UM013C-EN-P - August 2010
Chapter 8
Considerations When Replacing POINT Guard I/O Modules
If the project is configured for ‘Configure Always’, follow the appropriate steps to
replace a POINT Guard I/O module based on your scenario.
1.
Remove the old I/O module and install the new module.
2.
Right-click your POINT Guard I/O module and choose Properties.
3.
Click the Safety tab.
4.
Click Reset Ownership.
5.
Click OK.
6.
Follow your company-prescribed procedures to functionally test the
replaced I/O module and system and to authorize the system for use.
GuardLogix/
RSLogix 5000
Safety Signature
Exists
Replacement
Module SNN
Fault
Action Required
Yes or No
Out-of-box
None
None.
Yes or No
Same as original
None
None.
Yes or No
Different from original
SNN mismatch
Click Reset Ownership.
Follow the steps below.
Содержание 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S Installation User Manual...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013C EN P August 2010 Summary of Changes Notes...
Страница 38: ...38 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 2 Safety Functions Notes...
Страница 52: ...52 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 3 Install the Module Notes...
Страница 58: ...58 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 4 Wire the Module Notes...
Страница 64: ...64 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 5 Power Supply Examples Notes...
Страница 144: ...144 Rockwell Automation Publication 1734 UM013C EN P August 2010 Appendix D Specifications Notes...
Страница 153: ......
Страница 154: ......
Страница 155: ......