49
Install the Module
Chapter
3
4.
Browse to the DeviceNet network, being sure to
not
click OK when the
browse is complete.
If you are unable to browse the DeviceNet network and see the POINT
Guard modules, the modules may have been previously configured to an
incompatible data rate or node address. Attempt to add these modules on
an isolated network to determine the node address and data rate.
5.
Enter the current address for the device.
An out-of-box device uses address 63.
6.
Click OK
7.
Enter the new address for the device.
8.
Click Apply.
9.
Look for confirmation in the messages section.
7
8
9