116
Rockwell Automation Publication 1734-UM013C-EN-P - August 2010
Chapter 8
Considerations When Replacing POINT Guard I/O Modules
6.
Click OK.
This dialog box appears, confirming that the SNN has ben set.
The download now occurs. Once completed successfully, you see this
message in the main project view: ‘The device at address
xx
has been
downloaded. Any device-specific messages related to the download
operation are displayed separately.’
Assuming this is the proper configuration from the original DNT file, the
SNN and configuration signature now match that of the original. If you
are already connected to the SmartGuard controller, a connection is made.
The SmartGuard controller does not need to be taken out of RUN mode
to download to the replacement module.
If you download this configuration to a temporary setup, place the module
on the network and it automatically connects to the SmartGuard
controller.
Содержание 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S Installation User Manual...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013C EN P August 2010 Summary of Changes Notes...
Страница 38: ...38 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 2 Safety Functions Notes...
Страница 52: ...52 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 3 Install the Module Notes...
Страница 58: ...58 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 4 Wire the Module Notes...
Страница 64: ...64 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 5 Power Supply Examples Notes...
Страница 144: ...144 Rockwell Automation Publication 1734 UM013C EN P August 2010 Appendix D Specifications Notes...
Страница 153: ......
Страница 154: ......
Страница 155: ......