Rockwell Automation Publication 1734-UM013C-EN-P - August 2010
Chapter 8
Considerations When Replacing POINT Guard I/O Modules
Scenario 1 - New Module is Out-of-box and Safety Signature Exists
1.
Remove the old I/O module and install the new module.
2.
Right-click your POINT Guard I/O module and choose Properties.
3.
Click
to the right of the safety network number to open the Safety
Network Number dialog box.
4.
Click Set.
The Set Safety Network Number in Module confirmation dialog box
appears.
5.
Verify that the Network Status (NS) status indicator is alternating red/
green on the correct module before clicking Yes to set the SNN and accept
the replacement module.
6.
Follow your company-prescribed procedures to functionally test the
replaced I/O module and system and to authorize the system for use.
Содержание 1734-IB8S
Страница 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S Installation User Manual...
Страница 4: ...4 Rockwell Automation Publication 1734 UM013C EN P August 2010 Summary of Changes Notes...
Страница 38: ...38 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 2 Safety Functions Notes...
Страница 52: ...52 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 3 Install the Module Notes...
Страница 58: ...58 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 4 Wire the Module Notes...
Страница 64: ...64 Rockwell Automation Publication 1734 UM013C EN P August 2010 Chapter 5 Power Supply Examples Notes...
Страница 144: ...144 Rockwell Automation Publication 1734 UM013C EN P August 2010 Appendix D Specifications Notes...
Страница 153: ......
Страница 154: ......
Страница 155: ......