Chapter 3
Install the Module
Reset POINT Guard I/O
Modules to Out-of-box
Condition
It may be helpful to reset your POINT Guard I/O module to an out-of-box
condition before setting the modules node address on the DeviceNet network by
using the node commissioning tool. For example, if your POINT Guard I/O
module had a previous safety-connection owner, the module will not make a
safety connection to a new owner until the previous owner is cleared via a reset.
You can do this by using RSNetWorx for DeviceNet software.
Follow these steps to reset the module to an out-of-box condition.
1.
Right-click the module and choose Reset Safety Device.
2.
Check all of the options.
3.
Click Reset.