Chapter
6
Test Points
General
This chapter is intended to define the 1395 test points on the major boards to
help you troubleshoot the drive. A table of normal values for each test point
on each board is provided.
Main Control Board
The 1395 Main Control Board test points are common to all drive ratings.
Table 6.A Main Control Board Test Points
Test
Point Normal Value
Description
1
Not Used
Not Used
2
Full-wave rectified waveform from
Power Stage Interface Board, 2 volts =
Rated Armature Bridge Current (refer
to parameter 615).
ABSIA signal from Power Stage Interface
representing armature current feedback as sensed by
CTs on incoming 3 phase AC line.
3
Not Used
Not Used
4
DC Voltage between 0 and +5V DC.
Three-phase supply signal derived from half-wave
rectification of the 3 phase line to line voltages.
5
DC volts between 0 and +5V DC. Full
wave rectified three-phase waveform.
DC voltage representing armature current feedback
derived from the ABSIA signal. DC voltage is scaled
so that 4V DC represents 2 times full rated DC output
bridge current. See parameter 615, Rated Armature
Bridge Current.
6
0V DC when armature current is zero,
+5V DC when armature current is not
zero.
CURRZERO (NOT) signal used as a logic input to the
current control firmware for zero current detection.
This is a latched signal.
7
Not Used
Not Used
8
0V DC when phase loss detected, +5V
DC otherwise.
PHASE LOSS (NOT) signal used as a logic input to
the current control firmware for phase loss detection.
This is a latched signal.
9
0V DC when no DC overcurrent exists,
+5V DC when a DC overcurrent exists.
Output from overcurrent logic for DC current fault
detection.
10
Sawtooth type waveform varying
between 0 and +5V DC.
ARMCURRINTG signal representing the output of
the Charge Balance current feedback circuit used to
provide armature current feedback information for
control of armature current.
11
Not Used
Not Used
12
0 to +5V square-wave
ENCB signal indicating the frequency of the B
channel encoder feedback.
13
0 when encoder test is enabled, +5V
DC when encoder test is disabled (+5V
DC for normal operation).
ENCEN signal used to enable the injection of an
encoder test signal to the encoder feedback circuit.
ENCEN is logic 1 when the test operation is disabled
and the normal operation of the encoder feedback
signal is enabled.
14
DC voltage between 0 and +10V DC.
DC voltage representing DC armature current as
sensed by the DC current sensing device. DC voltage
scaling is set so that 8V DC represents 4 times full
rating of the armature bridge (this is the trip level).
This signal is used only for DC overcurrent detection.
Aotewell Ltd industry-mall.net
www.aotewell.com
www.aotewell.com
Содержание 1395
Страница 104: ...A 14 Parameter List Record Notes Aotewell Ltd industry mall net www aotewell com sales aotewell com www aotewell com ...
Страница 106: ...Index 2 Notes Aotewell Ltd industry mall net www aotewell com sales aotewell com www aotewell com ...
Страница 107: ...Aotewell Ltd industry mall net www aotewell com sales aotewell com www aotewell com ...