3-26
Malfunctions Not Indicated by a Fault
2.
Remove the pulse/snubber board by disconnecting the ribbon cable at J1
and remove the left and right gate leads at G1 and G2. Loosen the captive
thumb screws and remove the printed circuit board. Measure the
following resistances with the DVM on the 200 ohms scale. (Note lead
orientation is not critical)
If any of these measurements are out of tolerance, replace the associated
board. If the above procedure checks out and no apparent discrepancies
are found, a potential problem could still exist. If a “breakdown path”
has been established from the pulse transformer primary to the
secondary, it is possible that a malfunction could show itself when the
line voltage potential is applied to the power structure. This condition
can only be detected by “hi potting” the board at a level of 2500V rms,
and verifying less than 5 mA from primary to secondary.
115V Unit Power Supply (Series A)
The 115V Unit Power Supply sources the +5V, +12V, and +12V ISO logic
power supplies used on the 1395 printed circuit boards. It is located on the
fold down steel bracket, next to the PSI Board. A malfunction of this device
will exhibit loss of functionality due to low or non-existent logic supplies,
drive fault responses, and erratic operation. Follow the procedure below if a
unit power supply malfunction is suspected.
1.
Measure the 115V AC source for the power supply. With the DVM on
the 200V AC range, measure the voltage across J1 -5 and J1-6 on the PSI
Board. (No convenient test points exist on the unit power supply, most
measurements will be performed on the PSI board). If 115V AC cannot
be detected, check fuse F8 located on the top panel. Remove all power
prior to checking the condition of F8.
2.
Measure the outputs of the unit power supply. With the DVM on the 20
V DC range, measure the logic supply levels shown in
Table 3.A
referencing to TP5 (ground).
Important:
If necessary, the 5V level can be adjusted with potentiometer
R3, located on the Power Supply Board.
Measurement Point
Measurement
J1 Pin Orientation (Top View)
L1 to D3 (cathode)
100 ohms +/–10%
L1 to D3 (anode)
1 to 2 ohms
F1 to D4 (cathode)
100 ohms +/–10%
F1 to D4 (anode)
1 to 2 ohms
L3 to D2 (cathode)
100 ohms +/–10%
L3 to D2 (anode)
1 to 2 ohms
F1 to D1 (cathode)
100 ohms +/–10%
F1 to D1 (anode)
1 to 2 ohms
J1-1 to J1-9
60 ohms +/–10%
J1-1 to J1-10
60 ohms +/–10%
9 7 5 3 1
10 8 6 4 2
Arrow on header
Aotewell Ltd industry-mall.net
www.aotewell.com
www.aotewell.com
Содержание 1395
Страница 104: ...A 14 Parameter List Record Notes Aotewell Ltd industry mall net www aotewell com sales aotewell com www aotewell com ...
Страница 106: ...Index 2 Notes Aotewell Ltd industry mall net www aotewell com sales aotewell com www aotewell com ...
Страница 107: ...Aotewell Ltd industry mall net www aotewell com sales aotewell com www aotewell com ...