2-10
Malfunctions with Indications
SP-54
Processor PB
Faulted (Soft)
The Port B Adapter has been detected as
being in a faulted state. A controlled motor
stop will be initiated.
Check the Fault Queue to see if the
Adapter fault may have been recorded.
These faults must be corrected before
further operation. Execute a Clear Fault
and attempt normal operation. If the fault
reoccurs, replace the Port B Adapter. If
the fault reoccurs, replace the Main
Control Board.
SP-55
Processor PA
Faulted (Soft)
The Port A Adapter has been detected as
being in a faulted state. A controlled motor
stop will be initiated.
Check the Fault Queue to see if the
Adapter fault may have been recorded.
These faults should be corrected before
further operation. Execute System
RESET or cycle power and attempt
normal operation. If the fault reoccurs,
replace the Port A Adapter. If the fault
occurs again, replace the Main Control
Board.
SP-56
Illegal Mode
Request (Soft)
Internal processor communication error
detected. A controlled motor stop will be
initiated.
Execute a Clear Fault and continue
operation. If the fault reoccurs, replace
Main Control Board.
SP-57
Loc Mode Serial
Timeout (Soft)
This occurs when the Bulletin 1300
Programming Terminal is in LOCAL
CONTROL and serial communication is
interrupted. A controlled motor stop will be
initiated. This fault most often occurs when
the programming terminal has LOCAL
CONTROL and the serial cable to the drive
is unplugged or damaged.
Check the programming terminal
connection to the drive. The connector is
located next to the TB3 terminal strip on
the 1396. Also check the connection on
the programming terminal back if it is a
Door Mounted Terminal (DMT). Execute
a Clear Fault and continue operation. If
the fault reoccurs, replace the
Programming Terminal and/or cable. If
the fault reoccurs again, replace the
cable assembly from the Main Control
Board’s J4 to the D-Shell connector next
to TB3. If the fault is still persistent,
replace the Main Control Board.
SP-58
Task Timeout
(Hard)
Internal processor error detected. A
controlled motor stop will be initiated.
Execute System RESET or cycle power
and attempt normal operation. If the fault
reoccurs, replace Main Control Board.
SP-60
Processor VP
Hard (Hard)
The Velocity Processor has been detected
as being in a Hard Fault state and is
non-operational. A coast stop will be
initiated. This fault usually occurs when the
Velocity Processor has malfunctioned
during power-on diagnostics or has
experienced a major interruption of
operation.
Check the Fault Queue to see if the
Velocity Processor fault may have been
recorded. These faults must be corrected
before further operation. Execute System
RESET or cycle power and attempt
normal operation. Check TE & PE
grounding, if the fault continues to
reoccur, replace the Main Control Board.
SP-61
Processor CP
Hard (Hard)
The Current Processor has been detected
as being in a Hard Fault state and is
non-operational. A coast stop will be
initiated. This fault usually occurs when the
Current Processor has malfunctioned
during power-on diagnostics or has
experienced a major interruption of
operation.
Check the Fault Queue to see if the
Current Processor fault may have been
recorded. These faults must be corrected
before further operation. Execute System
RESET or cycle power and attempt
normal operation. Check TE & PE
grounding, if the fault continues to
reoccur, replace the Main Control Board.
System Processor Faults
No.
Name
Description
Recovery
Aotewell Ltd industry-mall.net
www.aotewell.com
www.aotewell.com
Содержание 1395
Страница 104: ...A 14 Parameter List Record Notes Aotewell Ltd industry mall net www aotewell com sales aotewell com www aotewell com ...
Страница 106: ...Index 2 Notes Aotewell Ltd industry mall net www aotewell com sales aotewell com www aotewell com ...
Страница 107: ...Aotewell Ltd industry mall net www aotewell com sales aotewell com www aotewell com ...