Publication 1394-5.0 — May 2000
Troubleshooting
9-9
Understanding GMC Turbo and
GMC Controller Faults
Use the table below to identify the GMC and GMC Turbo Controller
faults. The status LEDs are located inside the system module in the
upper left corner. The figure below shows a picture of the LEDs.
Figure 9.2
GMC Turbo and GMC Status LEDs
LED Status:
Potential cause:
Possible resolutions:
0:
1:
2:
Type:
Off
Off
Off
Solid
Controller OK - no faults
N/A
On
Off
Off
Solid
Memory fault - Setup or
program checksum error
Re-Download the GML diagram with the
setups
Reset the controller.
Off
On
Off
Solid
1394 Initialization
failure
Reset the controller. If problem persists, return
controller to the factory for repair.
On
On
Off
Solid
AxisLink initialization
failure
Reset the controller. If problem persists, return
controller to the factory for repair.
Off
Off
On
Solid
RIO interface
initialization failure
Reset the controller. If problem persists, return
controller to the factory for repair.
On
Off
On
Solid
Flex I/O initialization
failure
Reset the controller. If problem persists, return
controller to the factory for repair.
Off
On
On
Solid
Interrupt initialization
failure
Reset the controller. If problem persists, return
controller to the factory for repair.
On
On
On
Solid
DSP or initialization
failure
Reset the controller. If problem persists, return
controller to the factory for repair.
On
Off
Off
Flashing - fast
1
DRAM test #1 failed
Return the controller to the factory for repair.
Off
On
Off
Flashing - fast
1
DRAM test #2 failed
Return the controller to the factory for repair.
On
On
Off
Flashing -fast
1
DRAM test #3 failed
Return the controller to the factory for repair.
Off
Off
On
Flashing - fast
1
Applications memory
functionality test failed
Return the controller to the factory for repair.
On
Off
On
Flashing - fast
1
Setup memory
funcitonality test failed
Return the controller to the factory for repair.
Off
On
On
Flashing - fast
1
Dual port test #1 failed
Return the controller to the factory for repair.
On
On
On
Flashing - fast
1
Dual port test #2 failed
Return the controller to the factory for repair.
On
Off
Off
Flashing - slow
1
Serial port test failed
Return the controller to the factory for repair.
Off
On
Off
Flashing - slow
1
Timer test failed
Return the controller to the factory for repair.
On
On
Off
Flashing - slow
1
Initialization test failed
Return the controller to the factory for repair.
Off
Off
On
Flashing - slow
1
Auxiliary I/O test failed
Return the controller to the factory for repair.
On
Off
On
Flashing - slow
1
CXIC failed
Return the controller to the factory for repair.
Off
On
On
Flashing - slow
1
DRAM test failed
Return the controller to the factory for repair.
On
On
On
Flashing - slow
1
Transfer system failed
Return the controller to the factory for repair.
1
Flashing slow is twice per second, flashing fast is ten times per second.
Содержание 1394 SERCOS
Страница 1: ...User Manual 1394 Digital AC Multi Axis Motion Control System Catalog No 1394 50 Allen Bradley...
Страница 10: ...Publication 1394 5 0 May 2000 viii Table of Contents...
Страница 118: ...Publication 1394 5 0 May 2000 5 8 Wiring Your 1394 Analog Servo System...
Страница 124: ...Publication 1394 5 0 May 2000 6 6 Commissioning 1394 GMC and GMC Turbo Systems...
Страница 166: ...Publication 1394 5 0 May 2000 8 30 Configuring Your 1394 Analog Servo System...
Страница 232: ...Publication 1394 5 0 May 2000 A 34 Specifications...
Страница 292: ...Publication 1394 5 0 May 2000 D 14 Catalog Numbers...
Страница 300: ...I 8 Index Publication 1394 5 0 May 2000...