BEFORE CONNECTING MASTER/SLAVE COMMUNICATION WIRES, TAKE THE FOLLOWING STEPS:
1: Test and adjust the limit switches and ERDs for each operator as stand alone machines.
2: Once the machines have been adjusted, turn SLAVE dip switch “ON” to the slave board.
Press the RESET button on the slave board.
3: Connect the master/slave communication wires to “DATA -” and “DATA +”.
The “M/S LINK” LED should be “ON” on both machines.
4: Connect all accessories to the master operator. Accessories installed on the slave operator
will not work
.
.
USE UL LISTED CONDUIT
SHIELDED CABLE
CONNECT SHIELD TO
SLAVE OPERATOR
FRAME ONLY
MASTER BOARD
SLAVE BOARD
SLAVE SWITCH
ONLY ON
ON
SLAVE BOARD
MASTER/SLAVE CONNECTION