19
PROGRAMMABLE RELAY AND LEAF DELAY
S1
S2
RELAY FUNCTION
OFF
OFF
ONE SECOND PULSE FOR EVERY OPEN START
ON
OFF
ON WHEN GATE IS IN MOTION
OFF
ON
ALARM SYSTEM OUTPUT
ON
ON
ON WHEN GATE IS NOT FULLY CLOSED
1 2
OPEN
3
DEVICE
DEVICE
POWER SUPPLY
DIP SWITCH 3
OPENING AND CLOSING
DELAY FUNCTION SETTING
1
3
DELAY
0 TO 6 SECOND DELAY ADJUSTMENT
PROGRAMMABLE RELAY AND LEAF DELAY
RELAY SETTINGS
Board model ALL-BLDC includes a programmable relay
(N.O.) with four different configurations.
See table below for switch settings. Use the “Leaf Delay”
potentiometer to adjust the delay time from
0 to 6 seconds.
(1) 1 second pulse for every open start cycle
- Typically used for a cycle counter
(2) “ON” when the gate is in motion
- Typically used for an audible alarm or strobe light to
warn when the gate is in motion.
(3) Alarm system output
- Activates the relay when the gate is forced open
(4) “ON” when gate is not fully closed
- Typically used for a gate position indicator
DELAY SETTINGS
The ALL-BLDC board includes a delay option for open or
close cycles. This delay option is most commonly used
on swing gate applications. However, some slide gate
applications may require a pre-warn strobe light or siren.
In these applications this delay could be used for the
pre-warn delay in conjunction with the RELAY function
ON WHEN GATE IN MOTION.
Use the dip-switch 3 to set the desired delay direction.
•
Flip the dip-switch 3 to the OFF position for the
delay on opening direction
•
Flip the dip-switch 3 to the ON position for delay on
closing direction
•
Use leaf delay potentiometer to adjust the delay
•
It has adjustment from 0-6 seconds.
•
Turn clockwise for less time
•
Turn counter-clockwise for more time