14
LOOP LAYOUT
1/4 IN
1 1/2 IN
SAFETY LOOP
WHEN USED
EXIT LOOP
4 FT
4 FT
8 FT
8 FT
4 FT
4 FT
4 FT
GATE OPERATOR
GATE
GATE TRACK
TWISTED 6 TURNS
PER FOOT
NOTE:
IF WIRES ARE
NOT TWISTED, LOOP
WILL MALFUNCTION.
WIRED IN SERIES
OUTSIDE PROPERTY
SAFETY LOOP
—
Below is a typical loop layout. When connecting to an All-O-Matic circuit board, use the following:
—
SAFETY LOOP
- Normally Closed (N.C.) Contacts
—
EXIT/OPEN CMD
- Normally Open (N.O.) Contacts
(See page 27 for LPR-1 loop rack wiring)
—
Wires
MUST
be twisted from the exit point of the loop saw cut to the loop detector.
—
Twist loop wires 6 turns per foot, as shown below. Improper twisting of wires can cause loop issues.
—
When using an inside and outside safety loop, loops must be
WIRED IN SERIES
.
INSIDE PROPERTY