Swimming Pool Heat Pump Inverboost C /
21
7.5.
Filtration pump logic
Option 1; P3=0 Filtration pump is related to heat pump operation to start and stop.
Filtration pump starts 60s before compressor, filtration pump start 30s and then the water flow switch
detect flow. Before the heat pump enters into Standby mode, the compressor stops first and after 5
minutes filtration pump stops.
Option 2; P3=1 Filtration pump is always on, P2=0 the timer function is no active
Under condition P3=1, whenT1≥Tset+1°C(T1≥29°C) last for 3 minutes, heat pump will be in standby,
while filtration pump is always on.
Under option 2, with activation of the timer; P2=1 to start and stop the filtration pump according
the programming of the P4 (time), P5 (Timer ON) and P6 (Timer OFF)
Condition for the heat pump start, timer ON actives;
When the timer reaches the set time of TIMER ON, the filtration pump will start and after 5 minutes
the heat pump start. The heat pump stays in stop if the water in temperature is ≥ Tset+1°C, before the
TIMER OFF, the filtration still activated.
Condition to stop the heat pump, timer OFF actives;
Before the TIMER OFF, the heat pump stops and the filtration is still activated. When timer reaches the
set time of the TIMER OFF, the heat pump will stop and after 5 minutes the filtration pump stops.
NOTE:
Tset = Tseting water temperature, for example: Tset = 28°C Tseting water temperature in your pool
heat pump
Tset-0.5 = less 0.5°C than Tseting temperature, Tset- 0.5 = 28-0.5=27.5°C
Tset+0.5= more 1°C than Tseting temperature, Tset+ 0.5 = 28+0.5=28.5°C
Mode
Condition
Example
Water pump working logic
Heating
mode
P3=0,
T1≥Tset-0,5°C,
last for 30 minutes
P3=0,
T1≥27,5°C,
čeká 30 minut
1. Then it enters into
standby mode for
1 hour (It will not
restart except turn it on
manually.)
2. After 1 hour, the
filtration pump will
restart for 5 minutes. If
the T1≤27°C, the heat
pump will start to work
until T1≥27.5°C and last
for 30 minutes to go
into standby
Cooling
mode
P3=0,
T1≤Tset+0,5°C,
čeká 30 minut
P3=0,
T1≤28,5°C,
last for 30 minutes
1. Then it enters into
standby mode for
1 hour (It will not
restart except turn it on
manually.)
2. After 1 hour, the
filtration pump will
restart for 5 minutes.
If it tests T1≥29°C, the
heat pump will start to
work until T1≤28.5°C
and last for 30 minutes
to go into standby