Swimming Pool Heat Pump Inverboost C  / 

 

19

7.4.3. 

Button

 

and  

Lock / Unlock the display:

Hold 

 and 

 for 5 seconds to lock/unlock the display.

Water temperature setting:

Press  

  or  

 to set the water temperature directly.

Parameter checking:

Press  

 first, then press  

 to check the “ User parameter from d0 to d11

Remark:  d4: Frequency limitation code, 

0:  No frequency limit,

1:   Coil pipe temperature limit, 

2:  Overheating or overcooling frequency limit

  4   Drive Current frequency limit 

8:  Drive voltage frequency limit

16:   Drive high temperature frequency limit. 

Press 

  first, then press  

  to check/adjust the User parameter from P0 to P7

If needed, press  

  second, then press  

 or 

  to adjust the current parameter.

(for example: Press 

  first, then press  

 to enter parameter P7 checking, and press 

  second, 

then press  

  or 

 to adjust the parameter P7 Inlet water temp. Correction from -9 to 9.)

NOTE: Under defrosting mode, P0=1. After defrosting finished, it will be automatic enter Normal 
mode, P0=0. 

Code

Condition

Scope

Remark

d0

IPM mould temperature

0-120°C

Real testing value

d1

Inlet water temp.

-9°C~99°C

Real testing value

d2

Outlet water temp.

-9°C~99°C

Real testing value

d3

Ambient temp.

-30°C~70°C

Real testing value

d4

Frequency limitation code

0,1,2,4,8,16

Real testing value

d5

Piping temp.

-30°C~70°C

Real testing value

d6

Gas discharge temperature

0°C~C5°C (125°C)

Real testing value

d7

Step of EEV

0~99

N*5

d8

Compressor running frequency

0~99Hz

Real testing value

d9

Compressor current

0~30A

Real testing value

d10

Current fan speed

0-1200 (rpm)

Real testing value

d11

Error code for last time

All error code

Code

Name

Scope

Defaul

Remark

P0

Mandatory defrosting

0-1

0

0: Default normal operation
1: mandatory defrosting.

P1

Working mode

0-1

1

1:Heating mode, 
0:cooling mode, 

P2

Timer on/off

0-1

0

1 Timer on/off is under function.
0 Timer on/off is out of function 
(The setting of P5 and P6 won’t work)

P3

Water pump

0-1

0

1: Always running;
0: Depends on the running of compressor

P4

Current time

HH:MM

00:00

0-23:0-59

P5

Timer on

HH:MM

00:00

0-23:0-59

P6

Timer off

HH:MM

00:00

0-23:0-59

P7

Water temp. calibration

-9~9

0

Výchozí nastavení: 0

Содержание Inverboost C

Страница 1: ...Swimming Pool Heat Pump Inverboost C VERZE 17 01 2020 17 01 2020 EN INSTALLATION AND USER GUIDE...

Страница 2: ...ach piece of such equipment specifying the following information a The quantity and type of fluorinated greenhouse gases installed b The quantities of fluorinated greenhouse gases added during install...

Страница 3: ...l be damaged because of being frozen in such case your warranty will be lost 4 Please always cut the power supply if you want to open the cabinet to reach inside the heat pump 5 Please keep the displa...

Страница 4: ...Included with your Heat Pump Water connection assembly 50 mm pcs 2 User and service manual Drain connection qty 2 Drain hose qty 2 10 meters signal wire Waterproof box Anti vibration base pcs 4 1 2 D...

Страница 5: ...Swimming Pool Heat Pump Inverboost C 5 XHPFDPLUS160E...

Страница 6: ...and no fire source Heat pumps must be stored and transferred in vertical position in its original packaging If it is not the case it cannot be operated until a minimum period of 24H has passed before...

Страница 7: ...P 7 1 4 6 7 2 4 6 General data Compressor type MITSUBISHI MITSUBISHI Voltage V 220 240V 50Hz or 60Hz 1PH Rated current A 6 9 11 8 Minimum fuse A 10 18 Advised pool volume with pool cover m 12 33 25 8...

Страница 8: ...tool for the optimization of the heating of the water The valves allows the optimum flow of water using a manometer to make sure the optimized running of the compressor see paragraph 5 6 controls of t...

Страница 9: ...t the cables in the correct terminal according to electric diagram Filtration pump wiring Dry contact 1 Open the top cover of the heat pump 2 Connect the cables in the correct terminal according to el...

Страница 10: ...imum distance of the pump from the pool circulation pump is 7 5 metres Location and connection 5 ATTENTION Please observe the following rules when installing the heat pump 1 Any addition of chemicals...

Страница 11: ...sort must always be fitted in the piping on the downstream side of the heat pump and it is recommended to install a check valve to prevent reverse flow in the absence of water circulation Damage to t...

Страница 12: ...pplies only the heat pump All other components including a bypass if necessary must be provided by the user or the installer NOTE Item Product description 1 Heat pump 2 Water processor 3 Side connecti...

Страница 13: ...W V U JTAG RED RED I1 I2 OUT9 NO COM OUT6 OUT5 OUT4 N6 N5 N4 N2 N3 OUT3 N9 N1 OUT2 OUT1 COM OUT10 1 2 NO NO 3 TH1 TH2 TH5 TH4 TH3 TH8 TH7 TH6 NOTE 1 Above electrical wiring diagram only for your refe...

Страница 14: ...le This section is indicative and should be checked and adapted according to the needs and conditions of use The tolerance of acceptable voltage variation is 10 during operation The connections must b...

Страница 15: ...ops 1 degree below the set temperature for example if you set the temperature 28 C the heat pump will stop when the temperature at 29 C While it will restart when the temperature of the water down to...

Страница 16: ...mal value of the gas pressure R32 when the machine is in power off or running conditions The amount of condensation may be as much as several litres per hour at high relative humidity The condensate w...

Страница 17: ...to stop the heat pump unit and show OFF Notice During the parameter checking and setting press the to quick exit and save the current setting Press again to turn on off the machine 7 4 2 button Autom...

Страница 18: ...18 Swimming Pool Heat Pump Inverboost C Operation logic of Auto Mode Auto Mode Heating mode Logic of auto mode Heating Standby Heating Heating Cooling Standby Standby Tset 28 C...

Страница 19: ...Code Condition Scope Remark d0 IPM mould temperature 0 120 C Real testing value d1 Inlet water temp 9 C 99 C Real testing value d2 Outlet water temp 9 C 99 C Real testing value d3 Ambient temp 30 C 70...

Страница 20: ...when it is in operation 7 4 8 Symbol of automatic start the light will be on when it is in operation 7 4 9 Press this button the light will be flash the heat pump will operate in Full output only 7 4...

Страница 21: ...ted Condition to stop the heat pump timer OFF actives Before the TIMER OFF the heat pump stops and the filtration is still activated When timer reaches the set time of the TIMER OFF the heat pump will...

Страница 22: ...rotection Mode Output water temperature Set Point temperature Condition Malfunction Heating mode 36 C 29 C Tout Tset 7 C EE04 Overheating protection for water temperature T2 Cooling mode 23 C 30 C Tse...

Страница 23: ...uit 2 The wiring of sensor is loose 1 Check or change the sensor 2 Re fix the wiring of the sensors Exhaust piping sensor failure d6 TH3 PP06 1 The sensor in open or short circuit 2 The wiring of sens...

Страница 24: ...s blocked or pipe system is jammed 2 Fan motor speed is abnormal or fan motor is damaged under heating mode 3 Gas leakage 4 Low pressure wire is loose or damaged 1 Check the EEV and piping system Chec...

Страница 25: ...nection for compressor phase sequence 3 Compressor accumulations of liquid and oil lead to the current becomes larger 4 Compressor or driver board damaged 5 The water flow is abnormal 6 Power fluctuat...

Страница 26: ...Check if the power is in the normal range 2 Change driver board Input current over high protection EE13 1 The compressor current is too large momentary 2 The water flow is abnormal 3 Power fluctuatio...

Страница 27: ...s any barrier in front of fan blade and remove it PFC module thermal circuit is abnormal EE18 The driver board is damaged 1 Check if the motor speed is too low or fan motor is damaged replace it by a...

Страница 28: ...oard EE24 Ambient Temperature device failure Change driver board or main board Compressor phase failure EE25 Compressors U V W are just connected to one phase or two phases Check the actual wiring acc...

Страница 29: ...d no error code displays 1 Choose the wrong mode 2 Figures show defects 3 Controller defect 1 Adjust the mode to proper running 2 Replace the defect LED wire controller and then check the status after...

Страница 30: ...verboost C Exploded view 9 Model XHPFDPLUS100E 1 2 3 4 5 6 7 9 12 15 8 14 13 10 11 30 26 29 28 27 25 16 17 18 19 20 21 22 23 24 31 32 33 34 35 36 37 38 26 44 43 42 41 40 39 56 57 58 59 60 45 46 47 48...

Страница 31: ...ght side panel 26 Clip 27 Evaporator temperature sensor d3 TH2 28 Back panel 29 Cable ring 30 Cable connector NO Spare parts 31 Tube 32 Discharge temp sensor d6 TH3 33 Tube 34 Tube 35 EEV 36 Gas tube...

Страница 32: ...ump Inverboost C Model XHPFDPLUS160E 1 2 3 4 6 7 8 10 14 13 9 16 15 11 31 27 30 29 28 26 17 18 19 20 21 22 23 24 25 42 43 44 32 33 34 35 45 40 39 38 27 37 36 57 58 59 60 61 53 52 51 50 49 48 47 46 53...

Страница 33: ...26 Right side panel 27 Clip 28 Evaporator temperature sensor d3 TH2 29 Back panel 30 Cable ring 31 Cable connector NO Spare parts 32 Tube 33 Low pressure switch 34 Gas return pipe 35 Gas tube 36 High...

Страница 34: ...all installed technology of the swimming pool must not be exposed to temperatures below the freezing point It is necessary to remove all water from this whole system technology especially the heat and...

Страница 35: ...Swimming Pool Heat Pump Inverboost C 35 Notes...

Страница 36: ...Thank you for using ALBIXON products ALBIXON export albixon com www ALBIXON com Note that the photos used in the manual are illustrative only Printing and typesetting errors reserved...

Отзывы: