41
PARAMETER P04 – HEATING OUTPUT RISING TIME
6. Use buttons ‘+’ and ‘-‘ to modify the value of the parameter:
00 = 0 seconds
01 = 50 seconds (default)
02 = 100 seconds
03 = 200 seconds
04 = 400 seconds
7. Press and release button ‘S’ to con
fi
rm. The parameter
number (P04) will appear on the display.
8. Switch off the appliance and switch it back on again to render
the new parameter operative.
PARAMETER P05 – WATER HAMMER PREVENTION
FUNCTION
6. Use buttons ‘+’ and ‘-‘ to modify the value of the parameter:
00 = off
01 = on (default = 2 s.)
7. Press and release button ‘S’ to con
fi
rm. The parameter
number (P05) will appear on the display.
8. Switch off the appliance and switch it back on again to render
the new parameter operative.
PARAMETER P06 – D.H.W PRIORITY FUNCTION
It keeps 3 way valve in D.H.W. production position, for a period
equals to D.H.W. pump overrun, so that plate exchanger is
kept hot.
6. Use buttons ‘+’ and ‘-‘ to modify the value of the parameter:
00 = off
01 = on (default =120 s.);
7. Press and release button ‘S’ to con
fi
rm. The parameter
number (P06) will appear on the display.
8. Switch off the appliance and switch it back on again to render
the new parameter operative.
P 04
S
S
S
S
S
S
01
P 05
P 06
00
00
Содержание SERADENS SRD 20
Страница 1: ...SERADENS SRD 20 27 36 PREMIX CONDENSING BOILER INSTALLATION OPERATING and MAINTENANCE INSTRUCTIONS...
Страница 2: ...Code No A 1 4 3 Publishing Date 241109 Revision Date 241109...
Страница 31: ...31 80 48 5 313 48 5 111 5 187 111 5 80 163 137 122 106 131 SRD 36...
Страница 65: ...65 7 8 Troubleshooting...
Страница 67: ......