Installation and Operating Manual (translation)
38
AL-KO EASYAIR
®
6
Commissioning
6.1
Principles
During commissioning, all functions are checked, logged and signed by the operator. The signature also confirms the
handover of the Installation and Operating Manual These documents must be attached to the unit documentation.
WARNING
Accident and injury risk due to human misconduct.
Failure to observe the safety instructions, standards, directives and regulations leads to a risk
of injury.
Wear personal protective equipment.
Have work performed only by trained qualified staff.
Observe standards and directives.
Before commissioning, always ensure the following:
that the unit has been installed as described in this Installation and Operating Manual (see chapter
that all filter elements are properly installed.
that the duct system and the water and drain pipes are properly connected to the unit.
that the fresh air inlet is at a sufficient distance from contamination sources (kitchen hood extraction, central dust
extraction, etc.).
that the electrical installations have been implemented completely and professionally.
6.2
Before system start
WARNING
Risk of injury from fan during fan test run.
Never disassemble or bypass safety installations.
Work with care.
Remove any loose parts in the air handling unit.
Eliminate tripping hazards.
Maintain the safety distance.
Remain in the debris shadow when the fan starts up.
Wait until the fan impeller has come to a standstill.
Perform a vibration measurement of the fan impeller. If the permissible vibrations are ex-
ceeded, no commissioning may take place. Observe the table with the respective vibration
values (see chapter “3.2 Technical data” on page 14). Contact our customer service if
necessary.
Carry out a visual inspection for cracks in the impeller.
Wear personal protective equipment (ear protection).
Never brake the impellers of the fans by hand or using an object.
CAUTION
Risk of fire due to foreign objects on the electric heating register.
Before commissioning, check the electric heating register for foreign objects.
Содержание EASYAIR RO-01
Страница 1: ...COMPACT AIR HANDLING UNIT EN INSTALLATION AND OPERATING MANUAL AL KO EASYAIR EN ...
Страница 71: ...Subject to changes in line with technical progress 71 3313737 Notes ...
Страница 72: ...Installation and Operating Manual translation 72 AL KO EASYAIR Notes ...
Страница 73: ...Subject to changes in line with technical progress 73 3313737 Notes ...
Страница 74: ......
Страница 75: ......