Installation and Operating Manual (translation)
14
AL-KO EASYAIR
®
3
Product description
The exact type designation can be found on the type plates. The type plates are usually affixed to the housing. When
ordering spare parts or in case of other queries, please specify the type designation of the EASYAIR
®
unit, the year
of manufacture and the order number (see chapter “3.3 Sample EASYAIR® type plates” on page 18).
The EASYAIR
®
unit is suitable for operation in the temperature range from -20°C to +40°C.
The unit construction consists of two basic unit variants (with rotary heat exchanger or with plate heat exchanger).
Expansion modules (such as heat exchanger/cooler (both water-led), electric heating register, sound absorber, filter
or refrigerated part) are available as options. A more detailed explanation is given in sections 3.2.1 and 3.2.2. These
unit versions are available both for indoor installation and as a weatherproof unit version.
The customer-specific unit design can be found in the respective data sheets and drawings.
NOTE
Our products are subject to continuous quality control, and comply with the applicable reg-
ulations.
3.1
Functional description
EASYAIR
®
central ventilation and air handling units are compact and highly efficient air handling units with integrated
control. These are optionally also available without integrated control.
Both the air handling units with rotary heat exchanger and the units with countercurrent plate heat exchanger achieve
heat recovery rates of 80 – 90% according to DIN EN 308 (dry). The units therefore make a significant contribution to
saving energy and reducing costs. Sound emissions are minimised by a comprehensive insulation.
Optional components for extended use are: Sound-decoupled unit connection, suction hood with droplet eliminator and
tray, outlet hood, electric or water-heated heater module, heater/cooler module, filter module, refrigerated part, pressure
sensors for pressure or volume constant control, air quality sensor, room temperature sensor, etc.
Due filter changes are indicated by the differential pressure filter monitoring system. All control functions are prepared
and configurable in the control software. The control system can be easily integrated into higher-level systems via per
-
manently configured bus systems. The communication protocols Modbus, LON, Bacnet/IP are available.
3.2
Technical data
IMPORTANT
Read the documentation provided. There information on the technical and electrical data can
be found.
With the weatherproof unit design, the unit width widens by a total of 46 mm due to the roof overhang.
When optionally available connection frames are used, the unit length is extended by 65 mm on both sides.
Vibration values of the fan impeller
Installation
Machine group
Good
Usable
Still permissible
Rigid up to 15 kW
K
0.7 mm/s
1.8 mm/s
4.5 mm/s
Содержание EASYAIR RO-01
Страница 1: ...COMPACT AIR HANDLING UNIT EN INSTALLATION AND OPERATING MANUAL AL KO EASYAIR EN ...
Страница 71: ...Subject to changes in line with technical progress 71 3313737 Notes ...
Страница 72: ...Installation and Operating Manual translation 72 AL KO EASYAIR Notes ...
Страница 73: ...Subject to changes in line with technical progress 73 3313737 Notes ...
Страница 74: ......
Страница 75: ......