Description
Values
Min
Def
Max.
A
B
C
D
E
d9
Drip time at end of defrost (Page 12)
(compressor and fans off) (if P4
¹
1)
(min.)
0
1
255
No No Yes Yes Yes
d10
1st defrost start time (RTC required) (Page 12)
(h : min.)
00:00
Off
23:59 No No Yes
(1)
No Yes
d11
2nd defrost start time (RTC required) (Page 12)
(h : min.)
00:00
Off
23:59 No No
(1)
Yes No Yes
d12
3rd defrost start time (RTC required) (Page 12)
(h : min.)
00:00
Off
23:59 No No
(1)
Yes No Yes
d13
4th defrost start time (RTC required) (Page 12)
(h : min.)
00:00
Off
23:59 No No
(1)
Yes No Yes
d14
5th defrost start time (RTC required) (Page 12)
(h : min.)
00:00
Off
23:59 No No
(1)
Yes No Yes
d15
6th defrost start time (RTC required) (Page 12)
(h : min.)
00:00
Off
23:59 No No
(1)
Yes No Yes
EP
Exit Level 1
Description
Values
Min
Def
Max.
A
B
C
D
E
F0
Fan shut-down temperature as per probe 2
(if P4
¹
1) (Page 15)
(ºC/ºF)
-50
*
99,9 No No No Yes Yes
F1
Probe 2 differential (If P4
¹
1) (Page 15)
(ºC/ºF)
0,1
2,0
20,0 No No No Yes Yes
F2
Stop fans when stopping compressor
0
=No,
1
=Yes (Page 15)
0
1
1
No No No Yes Yes
F3
Fan status during defrost:
0
=Off;
1
=On
(Page 15)
0
*
1
No No No Yes Yes
F4
Starting delay after defrost (if F3=0) (Page 15)
Will only operate if it is higher than d9
(min.)
0
3
99
No No No Yes Yes
F5
Stop fans on opening the door
0
=No,
1
=Yes (Page 15)
(Requires a digital input configured as port P10 or P11=1)
0
0
1
No No No Yes Yes
EP
Exit Level 1
Description
Values
Min
Def
Max.
A
B
C
D
E
A0
Configuration of temperature alarms (Page 17):
0
=Relative to SP;
1
=Absolute
0
0
1
No No Yes Yes Yes
A1
Maximum alarm probe 1 (must be greater than SP) (Page 17)
(ºC/ºF)
NTC
A2
99,9
99,9
No No Yes
Yes Yes
PTC
-
150
No No
A2
Minimum alarm probe 1 (must be greater than SP) (Page 17)
(min.)
-50
-50
A1
No No Yes Yes Yes
A3
Temperature alarm delay during start-up (Page 18)
(min.)
0
0
120
No No Yes Yes Yes
A4
Temperature alarm delay after completion of
a defrost (Page 18)
(min.)
0
0
99
No No Yes Yes Yes
Level 2
Level 2
Level 2
Level 1.- Fan control
Level 1.- Alarm control (visual)
(1)
Only available with
, AKO-D14123-2-RC
26
A:
Available in
AKO-D14012 / D14023 / D14023C / D14024
D:
Available in
AKO-D14212 / D14220 / D14223 / D14312 / D14320 / D14323 / D14323-C / D10223 / D10323
C:
Available in
AKO-D14112 / D14123-2 / D14123-2-RC
E:
Available in
AKO-D14412-RC, AKO-D14423-RC
B:
Available in
AKO-D14120 / D14123 / D14124 / D14125 / D10123
Содержание -D101 Series
Страница 1: ...Thermometers and temperature controllers User Manual GB D144H002 Ed 03...
Страница 31: ......