background image

Defrost termination

The defrost will terminate if:

-The temperature programmed in parameter 24 has been reached in probe 2 (requires an additional input for 

the second probe and activating it via parameter P4).

-Time set in parameter d1 has passed (maximum duration of defrost).
-The 

key is pressed for 5 seconds.

Message displayed during defrost

Set by parameter d2, with the choice of showing the actual temperature detected by probe 1 (d2=0), displaying 
the temperature detected by  probe 1 at the start of defrost (d2=1) or displaying the DEF message (d2=2). The d3 
parameter defines the time during which the message is displayed, once the drip time (D9) and the fan stop time 
(F4) is over.

Parameter d5 allows users to specify if the unit will (d5=1) or will not (d5=0) defrost when powered up (initial 
start-up or after a power failure). In case of choosing option YES (d5=1), the defrost will start after the delay time 
specified in d6.

Using parameter d8, users define the computation of time in d0, choosing between total time elapsed (d8=0) or 
the total compressor running time (d8=1).

NOTE: 

If parameter d1 is set to 0, no defrost will be performed.

Defrosting is not performed if the controller is set to heat mode (P0=1)

It works the same way as defrost, but acts on the auxiliary relay (only if P6=1), controlled by probe 3 and serves to 
control defrost of a second evaporator.

Defrost Master - Slave

This feature allows users to synchronize defrost of several units. This is especially suitable for cabinets with multiple 
independently controlled evaporators, thus avoiding having an evaporator defrosting (generating heat) while the 
next is generating cold. 
When  the  main  controller  designated  as  Master  (P6=5)  initiates  a  defrost,  it  forces  the  rest,  which  must  be 
configured as slaves (P10 or P11=4), to initiate their defrost cycles.
When the main controller ends the defrost according to the time set by d1 (the temperature in probe 2 is not taken 
into account) it will force slaves to end defrosting and start synchronised drip time.
The master defrost function can only be set on 4-relay units and requires the use of an external relay (see diagram 
on next page).
Up to 15 units may be connected to a Master Controller and the maximum distance should not exceed 15 metres.

Other parameters

Second defrost  

(only 4-relay controllers)

13

Содержание -D101 Series

Страница 1: ...Thermometers and temperature controllers User Manual GB D144H002 Ed 03...

Страница 2: ...e electronic equipment to dust dirt water rain humidity high temperatures chemicals or corrosive sub stances of any sort Do not submit the equipment to blows or vibrations nor try to manipulate it dif...

Страница 3: ...nd various functions with keypad shortcuts EXTENDED FRAME models incorporate two switches for additional functions Ideal for controlling the turning on off of the cabinet lights etc Application AKO D1...

Страница 4: ...o normal In Standby mode the equipment performs no actions and onlythe indicatorisdisplayedonthescreen In programming menu allows you to scroll through the various levels or during the setting of a pa...

Страница 5: ...larm Temperature set in A2 has been reached p 17 and 18 Activates alarm relay Alternating with temperature Activates alarm relay External alarm activated by digital input p 17 and 18 Alternating with...

Страница 6: ...ire the maximum deviationwillbe0 25 C Wireforprobeextensionref AKO 15586 connecting 3 MODELS POWER SUPPLY PROBES DIGITAL INPUTS FORMAT NO OF KEYS RELAYS COMMUNICATION RTC ECO MODE AKO D14012 12 24V 1...

Страница 7: ...amming menu through P3 see Section 7 WARNING The default parameters by type of application have been defined for the most common applications Check that these parameters are suitable for your installa...

Страница 8: ...or product temperature probe controls defrost end temperature d4 of a second evaporator If second defrosting is not configured P6 1 Only available in 4 key controllers and if P4 2 or 3 Only available...

Страница 9: ...s energised on open contact Set time Only controllers with RTC The r1 and r2 parameters from the real time clock RTC settings adjust the local time of the controller The first r1 defines the hours and...

Страница 10: ...vated starting the heating resistors and leading to a rise in temperature Once the set point value SP is reached the COOL relay is turned off cutting power to the resistors Upon enabling this mode the...

Страница 11: ...er C5 In the event of probe 1 failure fault disconnection etc compressor performance will depend on C6 settings Users may choose between 3 options C6 0 The compressor will be stopped until probe 1 is...

Страница 12: ...or stops and the defrost takes place statically Fans will stop running regardless of parameter F3 By air d7 2 models with 2 or more relays Fans start running and the compressor starts up Defrost takes...

Страница 13: ...ning time d8 1 NOTE If parameter d1 is set to 0 no defrost will be performed Defrosting is not performed if the controller is set to heat mode P0 1 It works the same way as defrost but acts on the aux...

Страница 14: ...1 1 6 6 6 6 2 2 2 2 7 7 7 7 3 3 3 3 8 8 8 8 4 4 4 4 9 9 9 9 10 10 10 10 11 11 11 11 I max 16 A L N Settings d7 0 P4 2 P6 1 P10 4 Settings d7 0 P4 2 P6 1 P10 4 Settings d7 0 P4 2 P6 1 P10 4 Settings d7...

Страница 15: ...arameter F3 Parameter F4 defines the fan start up delay after defrost see section 4 2 4 4 Light control only controllers with two or more relays On units with 2 or more relays the auxiliary relay can...

Страница 16: ...he safety time set at P15 showing the message Art but it will continue to function normally STARTUP When temperature probe 1 reaches the set point value plus the differential SP C1 the AUX relay is ac...

Страница 17: ...when it reaches 8 degrees Displays the message AE external alarm or AES severe external alarm when the digital input configured as external alarm or severe external alarm is activated At least one of...

Страница 18: ...of external alarm activation A6 Delays the activation of the external alarm from the moment the digital input becomes active Delay of external alarm deactivation A7 Delays the deactivation of the ext...

Страница 19: ...AKO D14123 14125 10123 230 V 50 60 Hz 16 A Probe 1 1 2 3 4 5 6 COOL RES RES RES I max 16 A L N AKO D14123 2 230 V 50 60 Hz 2 CV S1 S2 or DI2 DI1 5 1 6 2 7 3 8 4 9 10 11 COOL C HEATER I max 16 A L N A...

Страница 20: ...223 230 V 50 60 Hz 5 4 3 relay controller AKO D14312 D14320 D14323 D10323 16 A 8 A 6 A S1 S2 or DI2 DI1 5 1 6 2 7 3 8 4 9 10 11 COOL FAN C HEATER AUX I max 16 A L N AUX COOL FAN C HEATER AUX I max 16...

Страница 21: ...es see table on page 6 have an RS485 MODBUS data connection port which allows users to manage them remotely via a PC with the AKO 5004 programme or an AKO 5005 server A different address must be assig...

Страница 22: ...programmed in L5 If the code entered is not correct the unit will revert to displaying the temperature 7 1 1 Changing the set point not available in thermometers Press the SET button for 5 seconds or...

Страница 23: ...arameters Level 3 Values Save changes Don t save changes 20 sec 20 sec OK OK OK OK Change value Level1 Menus Change menu Temperature Indication 10 seg SET SET SET SET 7 1 2 Changing the operating para...

Страница 24: ...Yes PTC 150 No No C0 Calibratingprobe1 Offset Page8 C F 20 0 0 0 20 0 Yes Yes Yes Yes Yes C1 Probe1differential Histeresis Page10 C F 0 1 2 0 20 0 No Yes Yes Yes Yes C2 Upperblockingofthesetpoint Page...

Страница 25: ...Yes Yes Yes d1 Maximumdefrostduration 0 defrostdeactivated Page 13 min 0 255 No Yes Yes Yes Yes d2 Typeofmessageduringdefrost Page13 0 Currenttemperature 1 Temperatureatstartofdefrost 2 DisplaydEFmess...

Страница 26: ...0 Off 1 On Page15 0 1 No No No Yes Yes F4 Startingdelayafterdefrost ifF3 0 Page15 Willonlyoperateifitishigherthand9 min 0 3 99 No No No Yes Yes F5 Stopfansonopeningthedoor0 No 1 Yes Page15 Requiresadi...

Страница 27: ...Yes Yes P2 Accesscode password functions Page9 0 Inactive 1 Blockaccesstoparameters 2 Keyboardlock 0 0 2 Yes Yes Yes Yes Yes P3 Setthedefaultparametersaccordingtothetypeofapplication Page7 1 Multipurp...

Страница 28: ...erpumpdown Page16 sec 1 10 999 No No No No Yes P15 Maximumpumpdowntime Page16 sec x 10 1 30 999 No No No No Yes EP ExitLevel1 Level 2 Description Values Min Def Max A B C D E r1 Clockconfiguration HOU...

Страница 29: ...14112 AKO D14212 D14312 D14412 RC AKO D14120 D14220 D14320 105 V 36 mA AKO D14023 D14024 D14123 D14123 2 D14124 D14125 D14223 D14323 D14023 C D14123 2 RC D14323 C D14423 RC D10123 D10223 D10323 207V 1...

Страница 30: ...mm 28 5 mm AKO D14012 D14023 D14024 D14120 D14123 D14124 D14125 D10123 Other models 20 8 mm 31 5 mm 20 4 mm 2 0 m m 2 1 mm 165 mm SET SET ESC ESC 79 mm 181 mm 38 mm 38 mm 8 1 Dimensions 8 2 Mounting...

Страница 31: ......

Страница 32: ...V 02 2011 AKO ELECTROMEC NICA S A L Av Roquetes 30 38 08812 Sant Pere de Ribes Barcelona Espa a Tel 34 938 142 700 Fax 34 938 934 054 e mail ako ako com www ako com Updated information on our website...

Отзывы: