4.2.- Defrost control 

(not available in thermometers)

On units with 1 relay, defrost can only be set by compressor shutdown.
On units with 2 or 3 relays, the auxiliary relay must be set as "defrost" (P6=1), except for 
defrost by compressor shutdown.

Defrost is initiated if:

-Time scheduled in parameter d0 has passed since the beginning of last defrost.
-It is time for one of its scheduled start-ups (parameters d10 to d15). This feature requires that d0 is set to 0 

(only units with RTC).

-The 

H

 key is pressed for 5 seconds

Defrost type

Selected by parameter d7 to define the controller performance during the defrost process.

Drip time

Parameter d9 sets drip time and the time added at the end of defrost cycle to allow for drainage of the remaining 
water in the evaporator. During this time the compressor and fans will not be running (unless defrost is by air).

Defrost start-up

By compressor shutdown

(d7=3)

The compressor stops and the defrost takes place statically.
Fans will stop running regardless of parameter F3.

By air

(d7=2)

(models with 2 or more relays)

Fans  start  running  and  the  compressor  starts  up.  Defrost  takes  place  by  air  being  forced 
through the evaporator.
Fans will be on regardless of parameter F3.

By resistors

(d7=0)

(models with 2 or more relays)

The defrost resistors start up and the compressor stops; defrost is the result of heat from the 
resistors. 
Fans will be running or not depending on parameter F3.

Reverse cycle (Heatpump)

(d7=1)

(models with 2 or more relays)

A 4-way valve is activated which reverses the cold-generating circuit and the compressor starts 
up, forcing the defrost.
Fans will be running or not depending on parameter F3.

By hot gas 

(d7=1)

(models with 2 or more relays)

A valve is actuated which discharges gas from the compressor to the evaporator inlet. A check 
valve prevents hot gas from returning to the liquid line.
Fans will be running or not depending on parameter F3.

12

CONTROL

time

ºC

F4

Max. d1

d3

d9

d0

SP

SP+C1

d4

DEFROST

DEFROST

DRIP

TIME

FAN START DELAY

“DEF” MESSAGE

CONTROL

CONTROL

Содержание -D101 Series

Страница 1: ...Thermometers and temperature controllers User Manual GB D144H002 Ed 03...

Страница 2: ...e electronic equipment to dust dirt water rain humidity high temperatures chemicals or corrosive sub stances of any sort Do not submit the equipment to blows or vibrations nor try to manipulate it dif...

Страница 3: ...nd various functions with keypad shortcuts EXTENDED FRAME models incorporate two switches for additional functions Ideal for controlling the turning on off of the cabinet lights etc Application AKO D1...

Страница 4: ...o normal In Standby mode the equipment performs no actions and onlythe indicatorisdisplayedonthescreen In programming menu allows you to scroll through the various levels or during the setting of a pa...

Страница 5: ...larm Temperature set in A2 has been reached p 17 and 18 Activates alarm relay Alternating with temperature Activates alarm relay External alarm activated by digital input p 17 and 18 Alternating with...

Страница 6: ...ire the maximum deviationwillbe0 25 C Wireforprobeextensionref AKO 15586 connecting 3 MODELS POWER SUPPLY PROBES DIGITAL INPUTS FORMAT NO OF KEYS RELAYS COMMUNICATION RTC ECO MODE AKO D14012 12 24V 1...

Страница 7: ...amming menu through P3 see Section 7 WARNING The default parameters by type of application have been defined for the most common applications Check that these parameters are suitable for your installa...

Страница 8: ...or product temperature probe controls defrost end temperature d4 of a second evaporator If second defrosting is not configured P6 1 Only available in 4 key controllers and if P4 2 or 3 Only available...

Страница 9: ...s energised on open contact Set time Only controllers with RTC The r1 and r2 parameters from the real time clock RTC settings adjust the local time of the controller The first r1 defines the hours and...

Страница 10: ...vated starting the heating resistors and leading to a rise in temperature Once the set point value SP is reached the COOL relay is turned off cutting power to the resistors Upon enabling this mode the...

Страница 11: ...er C5 In the event of probe 1 failure fault disconnection etc compressor performance will depend on C6 settings Users may choose between 3 options C6 0 The compressor will be stopped until probe 1 is...

Страница 12: ...or stops and the defrost takes place statically Fans will stop running regardless of parameter F3 By air d7 2 models with 2 or more relays Fans start running and the compressor starts up Defrost takes...

Страница 13: ...ning time d8 1 NOTE If parameter d1 is set to 0 no defrost will be performed Defrosting is not performed if the controller is set to heat mode P0 1 It works the same way as defrost but acts on the aux...

Страница 14: ...1 1 6 6 6 6 2 2 2 2 7 7 7 7 3 3 3 3 8 8 8 8 4 4 4 4 9 9 9 9 10 10 10 10 11 11 11 11 I max 16 A L N Settings d7 0 P4 2 P6 1 P10 4 Settings d7 0 P4 2 P6 1 P10 4 Settings d7 0 P4 2 P6 1 P10 4 Settings d7...

Страница 15: ...arameter F3 Parameter F4 defines the fan start up delay after defrost see section 4 2 4 4 Light control only controllers with two or more relays On units with 2 or more relays the auxiliary relay can...

Страница 16: ...he safety time set at P15 showing the message Art but it will continue to function normally STARTUP When temperature probe 1 reaches the set point value plus the differential SP C1 the AUX relay is ac...

Страница 17: ...when it reaches 8 degrees Displays the message AE external alarm or AES severe external alarm when the digital input configured as external alarm or severe external alarm is activated At least one of...

Страница 18: ...of external alarm activation A6 Delays the activation of the external alarm from the moment the digital input becomes active Delay of external alarm deactivation A7 Delays the deactivation of the ext...

Страница 19: ...AKO D14123 14125 10123 230 V 50 60 Hz 16 A Probe 1 1 2 3 4 5 6 COOL RES RES RES I max 16 A L N AKO D14123 2 230 V 50 60 Hz 2 CV S1 S2 or DI2 DI1 5 1 6 2 7 3 8 4 9 10 11 COOL C HEATER I max 16 A L N A...

Страница 20: ...223 230 V 50 60 Hz 5 4 3 relay controller AKO D14312 D14320 D14323 D10323 16 A 8 A 6 A S1 S2 or DI2 DI1 5 1 6 2 7 3 8 4 9 10 11 COOL FAN C HEATER AUX I max 16 A L N AUX COOL FAN C HEATER AUX I max 16...

Страница 21: ...es see table on page 6 have an RS485 MODBUS data connection port which allows users to manage them remotely via a PC with the AKO 5004 programme or an AKO 5005 server A different address must be assig...

Страница 22: ...programmed in L5 If the code entered is not correct the unit will revert to displaying the temperature 7 1 1 Changing the set point not available in thermometers Press the SET button for 5 seconds or...

Страница 23: ...arameters Level 3 Values Save changes Don t save changes 20 sec 20 sec OK OK OK OK Change value Level1 Menus Change menu Temperature Indication 10 seg SET SET SET SET 7 1 2 Changing the operating para...

Страница 24: ...Yes PTC 150 No No C0 Calibratingprobe1 Offset Page8 C F 20 0 0 0 20 0 Yes Yes Yes Yes Yes C1 Probe1differential Histeresis Page10 C F 0 1 2 0 20 0 No Yes Yes Yes Yes C2 Upperblockingofthesetpoint Page...

Страница 25: ...Yes Yes Yes d1 Maximumdefrostduration 0 defrostdeactivated Page 13 min 0 255 No Yes Yes Yes Yes d2 Typeofmessageduringdefrost Page13 0 Currenttemperature 1 Temperatureatstartofdefrost 2 DisplaydEFmess...

Страница 26: ...0 Off 1 On Page15 0 1 No No No Yes Yes F4 Startingdelayafterdefrost ifF3 0 Page15 Willonlyoperateifitishigherthand9 min 0 3 99 No No No Yes Yes F5 Stopfansonopeningthedoor0 No 1 Yes Page15 Requiresadi...

Страница 27: ...Yes Yes P2 Accesscode password functions Page9 0 Inactive 1 Blockaccesstoparameters 2 Keyboardlock 0 0 2 Yes Yes Yes Yes Yes P3 Setthedefaultparametersaccordingtothetypeofapplication Page7 1 Multipurp...

Страница 28: ...erpumpdown Page16 sec 1 10 999 No No No No Yes P15 Maximumpumpdowntime Page16 sec x 10 1 30 999 No No No No Yes EP ExitLevel1 Level 2 Description Values Min Def Max A B C D E r1 Clockconfiguration HOU...

Страница 29: ...14112 AKO D14212 D14312 D14412 RC AKO D14120 D14220 D14320 105 V 36 mA AKO D14023 D14024 D14123 D14123 2 D14124 D14125 D14223 D14323 D14023 C D14123 2 RC D14323 C D14423 RC D10123 D10223 D10323 207V 1...

Страница 30: ...mm 28 5 mm AKO D14012 D14023 D14024 D14120 D14123 D14124 D14125 D10123 Other models 20 8 mm 31 5 mm 20 4 mm 2 0 m m 2 1 mm 165 mm SET SET ESC ESC 79 mm 181 mm 38 mm 38 mm 8 1 Dimensions 8 2 Mounting...

Страница 31: ......

Страница 32: ...V 02 2011 AKO ELECTROMEC NICA S A L Av Roquetes 30 38 08812 Sant Pere de Ribes Barcelona Espa a Tel 34 938 142 700 Fax 34 938 934 054 e mail ako ako com www ako com Updated information on our website...

Отзывы: