1565H041 Ed.03
Description
Page
Units
Min
Def
Max.
Defrost at Start-up
19
No
Defrost delay at Start-up
19
(min.)
0
0
255
Signals end defrost time
18
No
Drip time
19
(min.)
0
1
255
Description
Page
Units
Min
Def
Max.
Fans stop temperature (controlled by probe 2)
(Probe 2 should be active)
20
(ºC/ºF)
–40.0
4.0
99.9
Fans differential s2
20
(ºC/ºF)
0.1
1.0
20.0
Stops when compressor OFF?
20
No
Fans state during defrost
Connected
Disconnected
20
Defrost
Fans delay after defrost
20
(min.)
0
3
255
Stop when opening door?
(It requires a digital input configured as door contact)
20
No
Description
Page
Units
Min
Def
Max.
Alarm configuration:
Relative to the SP
Absolute
22
Rel.
Maximum alarm in sensor 1 (limits according to the alarm configuration)
22
(ºC/ºF)
A. Min.
50.0
320
Minimum alarm in sensor 1 (limits according to the alarm configuration)
22
(ºC/ºF)
–40.0
50.0
A. Max.
Alarm differential
22
(ºC/ºF)
0.1
1.0
20.0
Temperature alarm delay
22
(min.)
0
30
255
Start-up alarm delay
22
(min.)
0
0
255
Alarm delay after defrost
22
(min.)
0
0
255
On-Off door alarm delay
22
(min.)
0
0
255
Off-On door alarm delay
22
(min.)
0
0
255
Alarm relay after key (After pressing the
ESC
key, alarm silenced):
Connected
Disconnected
22
Con.
FAN control
ALARM control
30
Содержание AKO-15650
Страница 35: ...1565H041 Ed 03 35 ...