1565H041 Ed.03

Description 

Page 

Units 

Min 

Def 

Max. 

Defrost at Start-up

19

No

Defrost delay at Start-up

19

(min.)

 

0

0

255

Signals end defrost time

18

No

Drip time

 

19

(min.)

 

0

1

255

Description 

Page 

Units 

Min 

Def 

Max. 

Fans stop temperature (controlled by probe 2)
(Probe 2 should be active)

 

20

(ºC/ºF)

 

–40.0

 

4.0

 

99.9

Fans differential s2

 

20

(ºC/ºF)

 

0.1

 

1.0

 

20.0

 

Stops when compressor OFF?

 

20

No

Fans state during defrost
 

Connected

 

Disconnected

 

20

Defrost

 

Fans delay after defrost

 

20

(min.)

 

0

3

255

Stop when opening door?
(It requires a digital input configured as door contact) 

20

No

Description 

Page 

Units 

Min 

Def 

Max. 

Alarm configuration:

 

Relative to the SP

 

Absolute

 

22

Rel.

 

Maximum alarm in sensor 1 (limits according to the alarm configuration)

 

22

(ºC/ºF)

 

A. Min.

 

50.0

 

320

Minimum alarm in sensor 1 (limits according to the alarm configuration)

 

22

(ºC/ºF)

 

–40.0

 

50.0

 

A. Max.

 

Alarm differential

 

22

(ºC/ºF)

 

0.1

 

1.0

 

20.0

 

Temperature alarm delay

22

(min.)

 

0

30

255

Start-up alarm delay

22

(min.)

 

0

0

255

Alarm delay after defrost

 

22

(min.)

 

0

0

255

On-Off door alarm delay

22

(min.)

 

0

0

255

Off-On door alarm delay

22

(min.)

 

0

0

255

Alarm relay after key (After pressing the 

ESC

 key, alarm silenced): 

 

  Connected 

Disconnected

 

22

Con.

 

FAN control 

ALARM control 

30

Содержание AKO-15650

Страница 1: ...AKO 1565x AKO 1568x AKO 1565x 1 AKO 1565x 3 PROPlus 3PH Electronic Panel GB 1565H042 Ed 03 User Manual ...

Страница 2: ...ordertoextendthelifetimeofourproductstothemaximum thefollowingpointsmustbeobserved Do not expose electronic equipment to dust dirt water rain moisture high temperatures chemical agents or corrosive substancesofanytype Do not subject equipment to knocks or vibrations or attempt to handle them in any way differently to that indicated in themanual Donotunderanycircumstancesexceedthespecificationsandl...

Страница 3: ...at should be replaced when the unit s battery life is under the duration assigned in its specifications At the end of the useful life of the unit the accumulators should be taken to a selectivewastecollectioncentreorreturnedtothemanufacturer 1 2 Cautions Usingtheunitnotobservingthemanufacturer sinstructionsmayaltertheappliance ssafetyrequirements Onlyprobes suppliedbyAKOshouldbeusedfortheittoopera...

Страница 4: ...651 4 6 3 A AKO 15652 6 3 10 A 10 200 W AKO 15653 10 16 A AKO 15680 2 5 4 A 7 000 W YES AKO 15681 4 6 3 A AKO 15682 6 3 10 A 10 200 W AKO 15683 10 16 A AKO 15650 1 2 5 4 A 7 000 W NO YES AKO 15651 1 4 6 3 A AKO 15652 1 6 3 10 A 10 200 W AKO 15653 1 10 16 A AKO 15651 3 4 6 3 A 0 63 1 A III N 7000 W YES NO AKO 15652 3 6 3 10 A 1 1 6 A III N 10 200 W AKO 15653 3 10 16 A 1 1 6 A III N AKO 15658 1 1 6 ...

Страница 5: ...emovecover B Using the included template make 4 holes in the wall and fasten the unit to the wall using the supplied screws Makeaholeinthebottomoftheboxtopassthecablesthrough andasuitableglandshouldbeusedtomainthe IP65degreeofprotection 355 255 5 ...

Страница 6: ...motor guard Q1 according to the obtained value The setvalueshouldneverbehigherthantheconsumptionindicatedbythemanufacturer 1 11 5 A A 2 3 I O 1 0 16 10 1 6 Q1 AKO 1565x AKO 1568x AKO 1565x 1 AKO 15658 AKO 15659 Motor guard adjustment Q3 Q3 Put an ammeter clamp into one of the fan s conductors Start the fan and check its consumption Set the motor guard Q3 according to the obtained value The set val...

Страница 7: ...ver be higher than the consumption indicated by the manufacturer If a fan is connected to the FAN 1 output Q1 will be adjusted to the sum of both consumptions FAN 1 compressor Q2 Put an ammeter clamp into one of the fan s conductors Start the fan and check its consumption Set the motor guard Q2 according to the obtained value The set value should never be higher than the consump tion indicated by ...

Страница 8: ... up Powersupplyvoltagesandfrequencieswillbetheonesthatfigureinthe Technicalspecifications section Checkthattherearenoloosepartsorforeignbodiesonconnectionsorswitchgear Checkthatthereisnodustordampinsidethepanel Checkthecorrectfasteningoftheswitchgearandcomponents Checkthecorrecttighteningofthescrewsandpowerconnections Checkthecorrectconnectionofthepowerconductors Checkthecorrectinsulationoftheoute...

Страница 9: ... display showsthemsymbolinthismode SET SET SET SET Pressing it for 5 seconds allows editing the descriptionoftheunit Seepage15 SET Pressing it for 5 seconds accesses the log list Seepage23 Pressing it for 5 seconds accesses the display contrastsetting pressNandQtochangeit SET SET Date Faulty or not connected flashing Loading Loading finished Battery status Time Status indicators Temperature Day of...

Страница 10: ...enuortochangethesetpoint DEFROST Indicatesthatadefrostisbeingperformed THERMOSTAT CONTROL Thethermostatcontrolfunctionisactive Seepage16 EXTERNALALARM SEVERE EXT ALARM Externalalarm severeexternalalarmactivatedbyoneofthedigitalinputs HIGHTEMP ALARM LOWTEMP ALARM The temperature of probe 1 exceeds is lower than the parameter programmed in Maximum alarm probe 1 Minimumalarmprobe1 L PRESSUREALARM The...

Страница 11: ...t breaker FM Operation circuit breaker Q1 Compressor motor guard Q2 Condenser fan motor guard Q3 Evaporator fan motor guard K1M Compressor contactor K2M Defrost contactor K3M Condenser fan contactor K4M Evaporator fan contactor T1 Insulation transformer D1 Phase detector Battery connector Probe and communications terminal Protections Phase detector Contactors Insulation transformer Control cable c...

Страница 12: ...658 59 Combine high low pressure controller preset option Separate Low pressure controller per AC input Separate Low pressure controller per digital input Pressure controller equivalence Pressure controller Dual HP LP Pressure controller LP indep AC input Configuration Configuration Configuration Pressure controller LP indep dig input Input 2 Low switch input Input 2 polarity Normally closed 6 6 9...

Страница 13: ...theselectiontotheright Displays the help for the selected parameter or function Moves the selection up or increases the value of the parameter Movestheselectiontotheleft Acceptsthevalueoraccessestheselectedmenu Allows exiting a parameter without saving the changes returning to the previous menu or exiting programming 8 Programming menu The programming menu allows adjusting the unit s parameters to...

Страница 14: ...See page 15 Ÿ Probes clock and text It displays all the active probes date time and day of the week and the description of the unit See page 15 The configuration of the Sensors to be displayed does not intervene in this mode Display unit It defines the temperature display units º Centigrade or º Fahrenheit Probe setting It defines the function of the inputs of probe S1 and S3 the function of the S...

Страница 15: ...s separate and is connected to the digital input 2 u Date If configures the current date year month day Hour If configures the current time day of the week day minute A Equipment description The unit s display can be customised including the description of the installation withamaximumlengthof25characters The description will not be displayed if the Display mode parameter is configured as Probe1an...

Страница 16: ...et point value SP plus the probe s differential the compressor solenoid is activated making the temperature drop When the set point value SP is reached the compressor solenoid stops When this mode is activated the compressor sole noid starts to operate continuously and without ta king the set point into account until the time confi gured in the continuous cycle duration parameter elapses or until ...

Страница 17: ...e compressor solenoid operates according to the times programmed in the following parameters Compresor ON error s1 Compressor solenoid time in operation in the event of fault in probe 1 Compresor OFF error s1 Compressor solenoid time stopped in the event of fault in probe 1 SET POINT LOCKINGS UsingtheSet Point upper limitandSet Point lower limitparameters itispossibletosetatopandbottomlimitfor the...

Страница 18: ... start of the last defrost TheparameterDefrost modedefineshowthistimeiscounted ž Frequency Total time passed between defrost starts ž Compressor sum Total time of the compressor solenoid operating between defrost starts ž Real Time Clock Defrost starts when one of the times programmed in the Defrost 1 to 8 on the u menu is reached The defrost frequency is not taken into account Ÿ We press the N ke...

Страница 19: ... defrost or display the DEFROSTmessage TheMessage durationparameterdefineshowlongthismessageisdisplayed afterthedriptimeandstartupdelayof thefans Seepage19 Other parameters Using the Defrost at Start up parameter you can configure if the unit carries out or not a defrost when it receives power firststartuporafterafaultinthepowersupply If the YES option is chosen defrost starts after the time defin...

Страница 20: ...latedparameters buttakingtherestoftheparametersintoaccount 9 4 Light control Theunithasanadditionalrelaytocontrolthecoldroom slights Justpressthe keytoturnthelightson off ThisfunctionisevenactivewhentheunitisinStand by Light timing The unit activates the lights whenever the cold room s door is detected to have been opened and turns them off after the time programmed in the Cold room light timing p...

Страница 21: ...int value plus the differential the liquid solenoid opens making the pressureintheevaporatorincreaseanddeactivatingthelowpressurecontroller whichwillstartthecompressorup When a balance is reached between the high and low pressure before the start up this is much gentler and lengthens thelifeofthecompressor If after a time after opening the liquid solenoid the low pressure controller does not deact...

Страница 22: ...olute the maximum temperature alarm activates when 10 degrees are reachedinprobe1 anddeactivateswhen8degreesarereached Delays Theydefinethedelaytimeinminutesfromacertainevent untiltheactivationofthetemperaturealarms Ÿ Temperature alarm delay Delayfromwhenthetemperatureisreached Ÿ Start up delay Delayfromwhichtheunitreceivespowersupply startuporafterafaultinthepowersupply This allowsstartingupthein...

Страница 23: ...ETtodisplaytheloggeddata Displayoftheloggeddata Defrost finished by time alarm The icon I is displayed when a defrost ends for maximum time The Signal end defrost time must be configured as Yes Thesoundalarmandalarmrelayisnotactivated Low pressure alarm It displays the LOW PRESSUREALARM message when low pressure is detected in the circuit or if pressure does not increase during the starting operat...

Страница 24: ...er for longer than indicated in the HACCP alarm delay parameter s menu theunitlogsanHACCPevent Ifthes flashes itindicatesthatanewHACCPeventhasbeenlogged Ifthiseventoccurscausedbyafaultinthepowersupply thisisindicatedinthelog Log date Log time Log value Log no First log 00 Last log 95 SET SET Scrolling through logs Log interval Last log date and time First log date and time Scale maximum Log value ...

Страница 25: ...ampleusinganexternalbutton ž Low pressure input It activates the low pressure alarm See page 23 and allows controlling the pump downfunction Seepage21 ž Thermostat control It uses this function to adjust the temperature using an external thermostat This functionisusuallyusedwhentherefrigeratorunithasitsownbuilt inthermostat Seepage16 Ÿ Input alarm delay 1 or 2 It defines the time that passes from ...

Страница 26: ...n of the unit using a 2 digit code from 01 to 99 If it is active a code is requested when you try to access the programming menu This menu cannot be accessed if a wrong value is entered The code is definedusingtheAccess passwordparameterofthe qmenu ThePassword to Set Pointparameterdefinesifthiscodeisrequestedonchangingthesetpoint 10 4 Return to initial parameters Thisfunctionconfiguresalltheunit s...

Страница 27: ...nect the programming key in the parameter server connector ž Connect the power supply for the programming key ž Press the READ key on the programming key ž Disconnect the device programming key Transfer parameters from the key to the equipment ž Disconnect the unit power supply ž Connect the programming key in the parameter server connector ž Connect the power supply for the programming key ž Pres...

Страница 28: ...er the software can be accessed from any PC in the network or even from Internet it requires the server having connection to InternetandfixedIP AKO 5012 Web server that includes the AKONet software It can carry out the same functions as the PC with the advantageofhavingaserverdedicatedtocommunicationwiththeunits If over 31 units are connected use an AKO 80024 connector ESC SET ESC SET A A B B A A ...

Страница 29: ...rs Temperature values are expressed in ºC equivalent temperature in ºF Description Page Units Min Def Max Set Point 16 ºC ºF 40 0 0 320 Sensor 1 differential 16 ºC ºF 0 1 1 0 20 0 Calibration of probe 1 13 ºC ºF 20 0 0 0 20 0 Set point upper limit it cannot be set above this value 17 ºC ºF B I 99 9 320 Set point lower limit it cannot be set below this value 17 ºC ºF 40 0 40 0 B S Compressor protec...

Страница 30: ... It requires a digital input configured as door contact 20 No Description Page Units Min Def Max Alarm configuration Relative to the SP Absolute 22 Rel Maximum alarm in sensor 1 limits according to the alarm configuration 22 ºC ºF A Min 50 0 320 Minimum alarm in sensor 1 limits according to the alarm configuration 22 ºC ºF 40 0 50 0 A Max Alarm differential 22 ºC ºF 0 1 1 0 20 0 Temperature alarm ...

Страница 31: ... Disabled Door contact External alarm Severe external alarm Remote defrost Remote energy saving Low pressure input Thermostat control 25 Input 2 alarm delay 25 min 0 0 255 Input 2 polarity Normally open The input is activated on closing the contact Normally closed The input is activated on opening the contact 25 NC Inact with door open time 25 min 0 0 255 Cold room light timing 20 min 0 0 255 Desc...

Страница 32: ...e sensor and text Sensor clock and text 14 S1 and r Display unit 14 ºC ºC ºF Decimal point 15 Yes Probe setting TEM at S1 REG at S3 Control probe connected in S1 and log probe in S3 TEM and REG at S3 Control and log probe connected in S3 14 TEM in S1 Delay at Start up 15 min 0 0 255 Type of operation not selectable Cold Program version Information 27 Program revision Information 27 GENERAL STATUS ...

Страница 33: ...m delay after a temperature alarm 0 Events log deactivated 24 min 0 1 255 HACCP Description Page Units Min Def Max Language Español English Français Deutsch 13 Description Page Units Min Def Max Date Year Month Day 15 Hour Day of the week Hour Minute 15 Defrost 1 Day Hour Minute 18 Defrost 2 Day Hour Minute 18 Defrost 3 Day Hour Minute 18 Defrost 4 Day Hour Minute 18 Defrost 5 Day Hour Minute 18 D...

Страница 34: ...ºC InputforNTCprobe AKO 14901 Maximuminputpowerintheoperation 30VA Workingambienttemperature 5ºCto40ºC Storageambienttemperature 30ºCto70ºC Overvoltagecategory IIs EN61439 1 Degreeofpollution IIs EN61439 1 Degreeofprotection IP65 Dimensions 400 An x300 Al x135 P mm Doubleisolationbetweenpowersupply secondarycircuitandrelayoutput Loggerbatterylifeifthepowersupplyfails 48hours Battery Li Polymerforl...

Страница 35: ...1565H041 Ed 03 35 ...

Страница 36: ...rials that might vary slightly to those described in our Technical Sheets Updated information is available on our website AKO ELECTROMECÁNICA S A L Avda Roquetes 30 38 08812 Sant Pere de Ribes Barcelona Spain Tel 34 902 333 145 Fax 34 938 934 054 www ako com ...

Отзывы: