1565H041 Ed.03
Drip time after defrost
This is establishing using the
Drip time
parameter of the
H
menu and defines the time added at the end of the defrost
to allow removing any water left in the evaporator.
During this time, the compressor/solenoid* and fans will be stopped (except if the defrost is by air).
Message displayed during defrost
This is established using the
Defrost message
parameter, and you can choose between displaying the real
temperature captured by probe 1, show the temperature capture by probe 1 at the start of the defrost, or display the
DEFROST message.
The
Message duration
parameter defines how long this message is displayed, after the drip time and start up delay of
the fans (See page 19).
Other parameters
Using the
Defrost at Start-up
parameter, you can configure if the unit carries out or not a defrost when it receives
power (first start up or after a fault in the power supply).
If the "YES" option is chosen, defrost starts after the time defined in the
Defrost delay at Start-up
parameter on the
H
menu.
Remote defrost
This function allows activating the defrost of the unit using an external button, connecting it to one of the digital inputs
that must be configured as "remote defrost”.
*In the panels
AKO-15658
/
15659
, the liquid solenoid is controlled instead of the compressor.
19